5990-00-782-0112 SYNCHRO,CONTROL TRANSFORMER Index 5925-00-782-0115 CIRCUIT BREAKER

National Stock Number:
5925-00-782-0113

Federal Supply Class:
5925

National Item Identification Number:
007820113

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
335C757H6179500WESTINGHOUSE ELECTRIC CORP
335C757H6197942NORTHROP GRUMMAN SYSTEMS CORPORATION
AM1774193EATON CORP HEINEMANN PRODUCTS COMMERCIAL CONTROLS DIV
AM17-2.0A74193EATON CORP HEINEMANN PRODUCTS COMMERCIAL CONTROLS DIV
DMS83059B16236DLA LAND AND MARITIME DBA ENGINEERING AND TECHNICAL SUPPORT DIV DOCUMENT STANDARDIZATION DIVISION (VENDOR ITEM DRAWINGS)


Techincal Specification:
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT POLE ONE
ARC QUENCHING METHODMAGNETIC BLOWOUT
BODY LENGTH2.500 INCHES NOMINAL
BODY STYLESINGLE POLE TYPE
BODY WIDTH0.750 INCHES NOMINAL
CASE MATERIALPLASTIC
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH1.190 INCHES NOMINAL
CIRCUIT PROTECTION TYPEOVERCURRENT SINGLE LOCATION
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH1.812 INCHES NOMINAL
FRAGILITY FACTORMODERATELY RUGGED
FREQUENCY IN HERTZ60.0 SINGLE LOCATION
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDEXPLOSION RESISTANT AND HERMETICALLY SEALED
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP SINGLE LOCATION
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITY1 TOGGLE
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS250.0 AC SINGLE LOCATION
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE2.0 AMPERES AC SINGLE LOCATION
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS3500.0 AC SINGLE LOCATION
MOUNTING FACILITY TYPE AND QUANTITY2 THREADED HOLE
MOUNTING SURFACE TO TERMINAL END DISTANCE2.000 INCHES NOMINAL
NOMINAL THREAD SIZE0.138 INCHES
POLE QUANTITY1
RESET METHODMANUAL
SPECIAL HANDLING FEATUREMAGNETIC
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
TERMINAL TYPE AND QUANTITY2 SCREW
TEST DATA DOCUMENT97942-335C757 DRAWING (THIS IS THE BASIC GOVERNING DRAWING, SUCH AS A CONTRACTOR DRAWING, ORIGINAL EQUIPMENT MANUFACTURER DRAWING, ETC.; EXCLUDES ANY SPECIFICATION, STANDARD OR OTHER DOCUMENT THAT MAY BE REFERENCED IN A BASIC GOVERNING DRAWING)
THREAD SERIES DESIGNATORUNC
THREAD QUANTITY PER INCH32
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT30.000 NOMINAL AT 150 PCT AND 12.000 NOMINAL AT 200 PCT AND 3.000 NOMINAL AT 300 PCT AND 1.500 NOMINAL AT 400 PCT SINGLE LOCATION
TRIP RELEASE CHARACTERISTICTIME DELAY SINGLE LOCATION
TRIP RELEASE METHODMAGNETIC-HYDRAULIC SINGLE LOCATION
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0 SINGLE LOCATION
ULTIMATE TRIP TIME PER POLE IN SECONDS60.000 NOMINAL SINGLE LOCATION