5925-00-782-0113 CIRCUIT BREAKER Index 6210-00-782-0118 LIGHT,INDICATOR

National Stock Number:
5925-00-782-0115

Federal Supply Class:
5925

National Item Identification Number:
007820115

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
483120-93B150RAYTHEON COMPANY
483120-949956RAYTHEON COMPANY
4MC2-7-3082647SENSATA TECHNOLOGIES, INC.
AM12MG6-30-50VDC574193EATON CORP HEINEMANN PRODUCTS COMMERCIAL CONTROLS DIV
APL-1-1-51-303-M81541SENSATA TECHNOLOGIES MARYLAND, INC
APL1-533-61081541SENSATA TECHNOLOGIES MARYLAND, INC


Techincal Specification:
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT POLE ONE
ARC QUENCHING METHODMAGNETIC BLOWOUT
BODY LENGTH2.500 INCHES NOMINAL
BODY STYLESINGLE POLE TYPE
BODY WIDTH0.750 INCHES NOMINAL
BOSS HEIGHT0.140 INCHES NOMINAL
CASE MATERIALPLASTIC
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH1.938 INCHES NOMINAL
CIRCUIT PROTECTION TYPEOVERCURRENT SINGLE LOCATION
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH20.062 INCHES NOMINAL
FRAGILITY FACTORMODERATELY RUGGED
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDDUSTPROOF AND FUNGUS PROOF
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP SINGLE LOCATION
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITY1 TOGGLE
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS65.0 DC SINGLE LOCATION
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE30.0 AMPERES DC SINGLE LOCATION
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS2000.0 DC SINGLE LOCATION
MOUNTING FACILITY TYPE AND QUANTITY2 THREADED HOLE
MOUNTING SURFACE TO TERMINAL END DISTANCE2.611 INCHES NOMINAL
NOMINAL THREAD SIZE0.138 INCHES
POLE QUANTITY1
RESET METHODMANUAL
SPECIAL HANDLING FEATUREMAGNETIC
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
TERMINAL TYPE AND QUANTITY2 THREADED STUD
THREAD PITCH DIAMETERS+0.1177 TO 0.1214 INCHES
THREAD SERIES DESIGNATORUNC
THREAD QUANTITY PER INCH32
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT0.120 MINIMUM AT 200 PCT AND 1.850 MAXIMUM AT 200 PCT SINGLE LOCATION
TRIP RELEASE CHARACTERISTICTIME DELAY SINGLE LOCATION
TRIP RELEASE METHODMAGNETIC-HYDRAULIC SINGLE LOCATION
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0 SINGLE LOCATION