BODY LENGTH | 1.562 INCHES MAXIMUM |
BODY STYLE | SINGLE POLE TYPE |
BODY WIDTH | 0.656 INCHES MAXIMUM |
BUSHING LENGTH | 0.380 INCHES MAXIMUM |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 0.875 INCHES NOMINAL |
CIRCUIT PROTECTION TYPE | OVERCURRENT SINGLE LOCATION |
FEATURES PROVIDED | NEUTRAL POLE, SWITCHABLE |
FREQUENCY IN HERTZ | 50.0 OR 60.0 SINGLE LOCATION |
INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP W/AUXILIARY LOAD TERMINAL SINGLE LOCATION |
MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 50.0 DC AND 240.0 AC SINGLE LOCATION |
PART NAME ASSIGNED BY CONTROLLING AGENCY | CAGE: AP/UP MAGNETIC CIRCUIT PROTECTOR |
MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 10000.0 AMPERES DC SINGLE LOCATION |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 40000.0 DC SINGLE LOCATION |
MOUNTING FACILITY TYPE AND QUANTITY | 1 THREADED BUSHING W/PANEL SEAL |
MOUNTING SURFACE TO TERMINAL END DISTANCE | 1.605 INCHES MAXIMUM |
NOMINAL THREAD SIZE | 0.375 INCHES |
POLE QUANTITY | 1 |
RESET METHOD | MANUAL |
SPECIAL FEATURES | AUXILIARY SWITCH RATING: 0.5 AMP AT 120 VAC OR 50 VDC |
TRIP RELEASE CHARACTERISTIC | TIME DELAY SINGLE LOCATION |
TRIP RELEASE METHOD | MAGNETIC SINGLE LOCATION |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 3.000 MINIMUM AT 135 PCT AND 60.000 MAXIMUM AT 135 PCT SINGLE LOCATION |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 800.0 SINGLE LOCATION |
SUPPLEMENTARY FEATURES | FULLY SEALED; WATERPROOF PANEL INTEGRITY PROVIDED BY O-RING BUSHING SEAL AND SILICON RUBBER GLAND WITHIN BUSHING/HANDLE ASSY |
TERMINAL TYPE AND QUANTITY | 2 WIRE HOOK |
THREAD SERIES DESIGNATOR | UNEF |