5930-01-562-2899 SWITCH,ROTARY Index 5330-01-562-2901 PACKING,PREFORMED

National Stock Number:
5925-01-562-2900

Federal Supply Class:
5925

National Item Identification Number:
015622900

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
WA5JHR33E9CFBBXXCX51918SCHNEIDER ELECTRIC USA, INC.
WA5JHR33E9CFBBXXCX6Z538CAROLINA POWER SYSTEMS OF SUMTER INC


Techincal Specification:
SPECIAL FEATURESBUS TIE AND SP BREAKERS, CIRCUIT BREAKER, 3200 AMPS, 3 POLE, ANSI, MASTERPACTNW, CONSISTING OF SQUARE D MASTERPACTS, DRAWOUT CIRCUIT BREAKER, 3000 AMP SENSOR PLUG, UL TYPE E RATING PLUG, MICROLOGIC TRIP UNIT, TYPE 5.0 WITH ZONE SELECTIVE PROTECTION, NO GROUND FAULT, 8 AUXILIARY CONTACTS, NO UNDERVOLTAGE TRIP, NO SECOND SHUNT TRIP, SPRING CHARGING MOTOR, 100-130 VAC, SHUNT TRIP, 24-30 VAC/VDC, CLOSING COIL 24-30 VAC/VDC, PADLOCKABLE PUSHBUTTON COVER, NO SECOND OVERCURRENT TRIP, TERMINATIONS FOR DRAWOUT BREAKER