National Stock Number: 5925-01-562-2885
Federal Supply Class: 5925
National Item Identification Number: 015622885
Description: CIRCUIT BREAKER
Detail: A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.
|
Manufacturer Information:
WA5JHR33E9DFBBXHCX | 51918 | SCHNEIDER ELECTRIC USA, INC. |
|
Techincal Specification:
POLE QUANTITY | 3 | SPECIAL FEATURES | GENERATOR BREAKER, CIRCUIT BREAKER 3200 AMPS, ANSI, CONSISTING OF SQUARE D MASTERPACT, DRAWOUT CIRCUIT BREAKER, 3000 AMP SENSOR PLUG, UL TYPE E RATING PLUG, MICROLOGIC TRIP UNIT, TYPE 5.0 WITH ZONE SELECTIVE PROTECTION, NO GROUND FAULT, 12 AUXILIARY CONTACTS,SPRING CHARGING MOTOR, 100-130 VAC, SHUNT TRIP, 24-30 VAC/VDC, CLOSING COIL, 24-30 VAC/VDC, ADJ TIME DELAY UNDERVOLTAGE TRIP 100-130 VAC, PADLOCKABLE PUSHBUTTON COVER, NO SECOND OVERCURRENT TRIP, TERMINATIONS FOR DRAWOUT BREAKER |
|
|