ACTUATOR FUNCTION | TRIP-RESET |
ACTUATOR POSITION DESIGNATION | AT POLE ONE |
BODY LENGTH | 2.000 INCHES NOMINAL |
BODY STYLE | SINGLE POLE TYPE |
BODY WIDTH | 0.755 INCHES NOMINAL |
BOSS HEIGHT | 0.130 INCHES NOMINAL |
CASE MATERIAL | PLASTIC |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.560 INCHES NOMINAL |
CIRCUIT PROTECTION TYPE | OVERCURRENT SINGLE LOCATION |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 1.660 INCHES NOMINAL |
FEATURES PROVIDED | HIGH INRUSH PROTECTION |
FREQUENCY IN HERTZ | 50.0 OR 60.0 SINGLE LOCATION |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | MOISTURE RESISTANT AND SALT SPRAY PROOF AND SHOCK RESISTANT AND VIBRATION RESISTANT |
INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP SINGLE LOCATION |
MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 277.0 AC SINGLE LOCATION |
MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 10.0 AMPERES AC SINGLE LOCATION |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 5000.0 AC SINGLE LOCATION |
MOUNTING FACILITY TYPE AND QUANTITY | 2 THREADED HOLE |
MOUNTING SURFACE TO TERMINAL END DISTANCE | 2.000 INCHES NOMINAL |
NOMINAL THREAD SIZE | 0.138 INCHES |
POLE QUANTITY | 1 |
RESET METHOD | MANUAL |
TRIP RELEASE CHARACTERISTIC | TIME DELAY SINGLE LOCATION |
TRIP RELEASE METHOD | MAGNETIC SINGLE LOCATION |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 2.200 MINIMUM AT 200 PCT AND 20.000 MAXIMUM AT 200 PCT SINGLE LOCATION |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 SINGLE LOCATION |
TERMINAL TYPE AND QUANTITY | 2 QUICK DISCONNECT, MALE |
THREAD SERIES DESIGNATOR | UNC |
THREAD QUANTITY PER INCH | 32 |