5925-01-353-2763 CIRCUIT BREAKER Index 5925-01-353-2765 CIRCUIT BREAKER

National Stock Number:
5925-01-353-2764

Federal Supply Class:
5925

National Item Identification Number:
013532764

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
404481-00293742DRS NAVAL POWER SYSTEMS, INC
BR22071183BRYANT ELECTRIC


Techincal Specification:
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONBETWEEN POLE ONE AND TWO
CASE MATERIALPLASTIC
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONS
FREQUENCY IN HERTZ60.0 ALL LOCATIONS
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP ALL LOCATIONS
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS240.0 AC ALL LOCATIONS
MANUAL ACTUATOR TYPE AND QUANTITY1 TOGGLE
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE20.0 AMPERES AC ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS22000.0 AC ALL LOCATIONS
POLE QUANTITY2
RESET METHODMANUAL
TRIP RELEASE CHARACTERISTICINSTANTANEOUS ALL LOCATIONS
TRIP RELEASE METHODMAGNETIC ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0 ALL LOCATIONS
TERMINAL TYPE AND QUANTITY4 COMPRESSION


Click here to Register for Free 30-day Trial