ACTUATOR FUNCTION | TRIP-RESET |
ACTUATOR POSITION DESIGNATION | BETWEEN POLE ONE AND TWO |
ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
BODY STYLE | RECTANGULAR DIMENSIONAL ENVELOPE |
CASE MATERIAL | PLASTIC |
CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
FRAGILITY FACTOR | MODERATELY RUGGED |
FREQUENCY IN HERTZ | 400.0 ALL LOCATIONS |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | DUSTPROOF AND FUNGUS PROOF |
INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 AC ALL LOCATIONS |
OVERALL HEIGHT | 1.384 INCHES MINIMUM AND 1.404 INCHES MAXIMUM |
OVERALL LENGTH | 1.810 INCHES MINIMUM AND 1.870 INCHES MAXIMUM |
OVERALL WIDTH | 1.550 INCHES MINIMUM AND 1.570 INCHES MAXIMUM |
MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 1.5 AMPERES AC ALL LOCATIONS |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 1000.0 AC ALL LOCATIONS |
MOUNTING FACILITY TYPE AND QUANTITY | 4 CLIP |
POLE QUANTITY | 2 |
RESET METHOD | MANUAL |
TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
TRIP RELEASE METHOD | MAGNETIC ALL LOCATIONS |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 150.0 ALL LOCATIONS |
STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
TERMINAL TYPE AND QUANTITY | 4 TAB, SOLDER LUG |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 1.000 MINIMUM AT 200 PCT AND 15.000 MAXIMUM AT 200 PCT ALL LOCATIONS |