5925-01-346-7825 CIRCUIT BREAKER Index 5925-01-346-7827 CIRCUIT BREAKER

National Stock Number:
5925-01-346-7826

Federal Supply Class:
5925

National Item Identification Number:
013467826

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
E23-B10030086L3HARRIS MARITIME POWER & ENERGY SOLUTIONS, INC.
ED23B10066842SIEMENS ENERGY AND AUTOMATION INC ITE CIRCUIT PROTECTION DIV


Techincal Specification:
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT POLE TWO
ARC QUENCHING METHODMAGNETIC BLOWOUT
BODY STYLERECTANGULAR DIMENSIONAL ENVELOPE
CASE MATERIALPLASTIC
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONS
FRAGILITY FACTORMODERATELY RUGGED
FREQUENCY IN HERTZ60.0 ALL LOCATIONS
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDDUSTPROOF AND FUNGUS PROOF
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP ALL LOCATIONS
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS240.0 AC ALL LOCATIONS
OVERALL HEIGHT3.000 INCHES NOMINAL
OVERALL LENGTH6.343 INCHES NOMINAL
OVERALL WIDTH4.406 INCHES NOMINAL
MANUAL ACTUATOR TYPE AND QUANTITY1 TOGGLE
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE100.0 AMPERES AC ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS10000.0 AC ALL LOCATIONS
MOUNTING FACILITY TYPE AND QUANTITY4 UNTHREADED HOLE
POLE QUANTITY3
RESET METHODMANUAL
SPECIAL HANDLING FEATUREMAGNETIC
TRIP RELEASE CHARACTERISTICINSTANTANEOUS ALL LOCATIONS
TRIP RELEASE METHODMAGNETIC ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0 ALL LOCATIONS
UNTHREADED MOUNTING HOLE DIAMETER0.196 INCHES NOMINAL
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
TERMINAL TYPE AND QUANTITY6 COMPRESSION