ACTUATOR FUNCTION | TRIP-RESET |
ACTUATOR POSITION DESIGNATION | AT POLE TWO |
ADJUSTABLE TRIP SETTING CURRENT RANGE PER POLE IN AMPS | +180.0 TO 600.0 AC ALL LOCATIONS |
ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
BODY STYLE | RECTANGULAR DIMENSIONAL ENVELOPE |
CASE MATERIAL | PLASTIC |
CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
FEATURES PROVIDED | ADJUSTABLE TRIP RELEASE |
FRAGILITY FACTOR | MODERATELY RUGGED |
FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | DUSTPROOF |
INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 600.0 AC AND 250.0 DC ALL LOCATIONS |
OVERALL HEIGHT | 3.000 INCHES NOMINAL |
OVERALL LENGTH | 6.344 INCHES NOMINAL |
OVERALL WIDTH | 4.406 INCHES NOMINAL |
MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 50.0 AMPERES AC AND 50.0 AMPERES DC ALL LOCATIONS |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 18000.0 AC AND 30000.0 DC ALL LOCATIONS |
MOUNTING FACILITY TYPE AND QUANTITY | 4 UNTHREADED HOLE |
POLE QUANTITY | 3 |
RESET METHOD | MANUAL |
SPECIAL HANDLING FEATURE | MAGNETIC |
TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS ALL LOCATIONS |
TRIP RELEASE METHOD | MAGNETIC ALL LOCATIONS |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
UNTHREADED MOUNTING HOLE DIAMETER | 0.219 INCHES NOMINAL |
STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
TERMINAL TYPE AND QUANTITY | 6 COMPRESSION |