ACTUATOR FUNCTION | TRIP-RESET |
ACTUATOR POSITION DESIGNATION | AT POLE TWO |
ADJUSTABLE TRIP SETTING CURRENT RANGE PER POLE IN AMPS | +1250.0 TO 2500.0 AC ALL LOCATIONS |
ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
BODY HEIGHT | 4.370 INCHES NOMINAL |
BODY LENGTH | 14.750 INCHES NOMINAL |
BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
BODY WIDTH | 6.000 INCHES NOMINAL |
BOSS HEIGHT | 1.970 INCHES NOMINAL |
CASE MATERIAL | PLASTIC |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 9.250 INCHES NOMINAL |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 2.000 INCHES NOMINAL |
CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 9.250 INCHES NOMINAL |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 1.000 INCHES NOMINAL |
FEATURES PROVIDED | ADJUSTABLE TRIP RELEASE |
FRAGILITY FACTOR | MODERATELY RUGGED |
FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | DUSTPROOF |
MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 600.0 AC AND 250.0 DC ALL LOCATIONS |
MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 250.0 AMPERES AC AND 250.0 AMPERES DC ALL LOCATIONS |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 18000.0 AC ALL LOCATIONS |
MOUNTING FACILITY TYPE AND QUANTITY | 4 UNTHREADED HOLE |
POLE QUANTITY | 3 |
RESET METHOD | MANUAL |
SPECIAL HANDLING FEATURE | MAGNETIC |
TRIP RELEASE AMBIENT TEMP RATING | 40.0 CELSIUS NOMINAL ALL LOCATIONS |
TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS ALL LOCATIONS |
TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
UNTHREADED MOUNTING HOLE DIAMETER | 0.196 INCHES NOMINAL |
STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
TERMINAL TYPE AND QUANTITY | 6 COMPRESSION |