5910-01-261-7870 CAPACITOR,FIXED,ELECTROLYTIC Index 5925-01-261-7872 CIRCUIT BREAKER

National Stock Number:
5925-01-261-7871

Federal Supply Class:
5925

National Item Identification Number:
012617871

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
216556-994987CUBIC DEFENSE APPLICATIONS, INC.
44-200-P10-S1-043.800-2006402OAKLAND INDUSTRIES LTD


Techincal Specification:
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT POLE ONE
AUXILIARY SWITCH FUNCTION AND QUANTITY1 ALARM
BODY LENGTH19.8 MILLIMETERS NOMINAL
BODY STYLESINGLE POLE TYPE
BODY WIDTH15.8 MILLIMETERS NOMINAL
BUSHING LENGTH6.5 MILLIMETERS NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH12.7 MILLIMETERS NOMINAL
CIRCUIT PROTECTION TYPEOVERCURRENT SINGLE LOCATION
CRITICALITY CODE JUSTIFICATIONFEAT
FREQUENCY IN HERTZ400.0 SINGLE LOCATION
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDGENERAL PURPOSE
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP SINGLE LOCATION
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITY1 PUSH-PULL
MATERIALPLASTIC CASE
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE100.0 MILLIAMPERES AC AND 100.0 MILLIAMPERES DC SINGLE LOCATION
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS1000.0 AC AND 1000.0 DC SINGLE LOCATION
MOUNTING FACILITY TYPE AND QUANTITY1 THREADED BUSHING
MOUNTING SURFACE TO TERMINAL END DISTANCE43.5 MILLIMETERS NOMINAL
NOMINAL THREAD SIZE12.0 MILLIMETERS
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS250.0 AC AND 28.0 DC SINGLE LOCATION
SPECIAL FEATURESAMPS MARKED ON ITEM IS FOR TRAINING ONLY
POLE QUANTITY1
RESET METHODMANUAL
SWITCH CONTACT ARRANGEMENTDOUBLE POLE, DOUBLE THROW
SWITCH CURRENT RATING AND TYPE IN AMPS1.0 AC AND 5.0 DC
SWITCH LOCATION AND POSITION DESIGNATIONINTERNAL AT POLE ONE
SWITCH TERMINAL TYPEQUICK DISCONNECT, MALE
SWITCH VOLTAGE RATING AND TYPE IN VOLTS220.0 AC AND 28.0 DC
TERMINAL TYPE AND QUANTITY2 QUICK DISCONNECT, MALE
THREAD PITCH IN MILLIMETERS1.25
THREAD SERIES DESIGNATORISO M
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT15.000 MINIMUM AT 200 PCT AND 60.000 MAXIMUM AT 200 PCT SINGLE LOCATION
TRIP RELEASE AMBIENT TEMP RATING150.0 FAHRENHEIT NOMINAL SINGLE LOCATION
TRIP RELEASE CHARACTERISTICTIME DELAY SINGLE LOCATION
TRIP RELEASE METHODTHERMAL SINGLE LOCATION
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT140.0 SINGLE LOCATION