ADJUSTABLE TRIP SETTING CURRENT RANGE PER POLE IN AMPS | +1500.0 TO 3000.0 AC ALL LOCATIONS |
ARC QUENCHING METHOD | DEION |
BODY STYLE | RECTANGULAR DIMENSIONAL ENVELOPE |
CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CRITICALITY CODE JUSTIFICATION | FEAT |
FEATURES PROVIDED | ADJUSTABLE TRIP RELEASE |
FRAGILITY FACTOR | MODERATELY RUGGED |
FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 500.0 AC ALL LOCATIONS |
OVERALL HEIGHT | 3.785 INCHES NOMINAL |
OVERALL LENGTH | 8.438 INCHES NOMINAL |
OVERALL WIDTH | 5.625 INCHES NOMINAL |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 150.0 AMPERES AC ALL LOCATIONS |
MOUNTING FACILITY TYPE AND QUANTITY | 5 UNTHREADED HOLE |
POLE QUANTITY | 3 |
SPECIAL FEATURES | FOR USE WITH NEW STYLE A FUSES ONLY |
STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
TERMINAL TYPE AND QUANTITY | 6 SCREW |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 25.000 NOMINAL AT 600 PCT ALL LOCATIONS |
TRIP RELEASE AMBIENT TEMP RATING | 50.0 CELSIUS NOMINAL ALL LOCATIONS |
TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS AND TIME DELAY ALL LOCATIONS |
TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 105.00 ALL LOCATIONS |
UNTHREADED MOUNTING HOLE DIAMETER | 0.203 INCHES MINIMUM AND 0.438 INCHES MAXIMUM |