POLE QUANTITY | 3 |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 20.0 AMPERES AC ALL LOCATIONS |
CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
TERMINAL TYPE AND QUANTITY | 6 THREADED STUD |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 480.0 AC ALL LOCATIONS |
TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
RESET METHOD | MANUAL |
BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
MOUNTING FACILITY TYPE AND QUANTITY | 6 THREADED HOLE |
CASE MATERIAL | PLASTIC |
UNPACKAGED UNIT WEIGHT | 9.500 OUNCES NOMINAL |
TRIP RELEASE METHOD | MAGNETIC ALL LOCATIONS |
FREQUENCY IN HERTZ | 50.0 OR |
| 60.0 ALL LOCATIONS |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 5000.0 AC ALL LOCATIONS |
INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 2.200 MINIMUM AT 200 PCT AND |
| 20.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
BODY LENGTH | 2.490 INCHES NOMINAL |
BODY WIDTH | 2.265 INCHES MAXIMUM |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.940 INCHES NOMINAL |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.750 INCHES NOMINAL |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.060 INCHES NOMINAL |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 0.750 INCHES NOMINAL |
BOSS HEIGHT | 0.150 INCHES NOMINAL |
MOUNTING SURFACE TO TERMINAL END DISTANCE | 2.475 INCHES NOMINAL |
THREAD SERIES DESIGNATOR | UNC |
NOMINAL THREAD SIZE | 0.138 INCHES |
THREAD QUANTITY PER INCH | 32 |
MANUAL ACTUATOR TYPE AND QUANTITY | 3 TOGGLE |
ACTUATOR FUNCTION | TRIP-RESET |
ACTUATOR POSITION DESIGNATION | AT EACH POLE |
EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE, TWO, AND THREE LINKED |
AUXILIARY SWITCH FUNCTION AND QUANTITY | 1 ALARM |
SWITCH LOCATION AND POSITION DESIGNATION | INTERNAL AT POLE THREE |
SWITCH CONTACT ARRANGEMENT | SINGLE POLE, DOUBLE THROW |
SWITCH CURRENT RATING AND TYPE IN AMPS | 10.0 AC AND |
| 3.0 DC |
SWITCH VOLTAGE RATING AND TYPE IN VOLTS | 250.0 AC AND |
| 50.0 DC |
SWITCH TERMINAL TYPE | TAB, SOLDER LUG |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | DUSTPROOF |
FEATURES PROVIDED | HIGH INRUSH PROTECTION |
ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
FRAGILITY FACTOR | MODERATELY RUGGED |