5925-01-216-2170 CIRCUIT BREAKER Index 5999-01-216-2173 GASKETING MATERIAL,CONDUCTIVE

National Stock Number:
5925-01-216-2172

Federal Supply Class:
5925

National Item Identification Number:
012162172

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
AP-12-1RC-65F-20381541SENSATA TECHNOLOGIES MARYLAND, INC


Techincal Specification:
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONBETWEEN POLE ONE AND TWO
ARC QUENCHING METHODMAGNETIC BLOWOUT
AUXILIARY SWITCH FUNCTION AND QUANTITY1 ALARM
BODY LENGTH1.500 INCHES MAXIMUM
BODY STYLEMULTIPOLE-SINGLE ACTUATOR TYPE
BODY WIDTH1.250 INCHES MAXIMUM
BUSHING LENGTH0.380 INCHES MAXIMUM
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH0.860 INCHES MINIMUM AND 0.890 INCHES MAXIMUM
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH0.610 INCHES MINIMUM AND 0.640 INCHES MAXIMUM
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONS
FRAGILITY FACTORMODERATELY RUGGED
FREQUENCY IN HERTZ60.0 ALL LOCATIONS
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDHERMETICALLY SEALED AND SHOCK RESISTANT AND VIBRATION RESISTANT
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP ALL LOCATIONS
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS240.0 AC ALL LOCATIONS
MANUAL ACTUATOR TYPE AND QUANTITY1 TOGGLE
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE20.0 AMPERES AC ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS1000.0 AC ALL LOCATIONS
MOUNTING FACILITY TYPE AND QUANTITY1 THREADED BUSHING W/PANEL SEAL
MOUNTING SURFACE TO TERMINAL END DISTANCE1.780 INCHES MAXIMUM
NOMINAL THREAD SIZE0.375 INCHES
NONTURN DEVICE DIAMETER0.235 INCHES MINIMUM AND 0.265 INCHES MAXIMUM
NONTURN DEVICE LENGTH0.130 INCHES NOMINAL
NONTURN DEVICE RADIUS0.610 INCHES MINIMUM AND 0.640 INCHES MAXIMUM
POLE QUANTITY2
RESET METHODMANUAL
SPECIAL HANDLING FEATUREMAGNETIC
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
SWITCH CONTACT ARRANGEMENTSINGLE POLE, DOUBLE THROW
SWITCH CURRENT RATING AND TYPE IN AMPS0.5 AC AND 0.5 DC
SWITCH LOCATION AND POSITION DESIGNATIONINTERNAL AT POLE TWO
SWITCH TERMINAL TYPEWIRE HOOK
SWITCH VOLTAGE RATING AND TYPE IN VOLTS120.0 AC AND 50.0 DC
TERMINAL TYPE AND QUANTITY4 WIRE HOOK
THREAD QUANTITY PER INCH32
THREAD PITCH DIAMETERS+0.3503 TO 0.3537 INCHES
THREAD SERIES DESIGNATORUNEF
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT1.200 MINIMUM AT 200 PCT AND 7.500 MAXIMUM AT 200 PCT ALL LOCATIONS
TRIP RELEASE CHARACTERISTICTIME DELAY ALL LOCATIONS
TRIP RELEASE METHODMAGNETIC ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT115.0 ALL LOCATIONS
UNPACKAGED UNIT WEIGHT3.600 OUNCES NOMINAL


Click here to Register for Free 30-day Trial