5925-01-213-6396 CIRCUIT BREAKER Index 5925-01-213-6398 CIRCUIT BREAKER

National Stock Number:
5925-01-213-6397

Federal Supply Class:
5925

National Item Identification Number:
012136397

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
17001-0306YY5THALES TRAINING & SIMULATION INC
17001-0382932THOMSON TRAINING AND SIMULATION INC DBA BURTEK
T11-1-15.00A-01-89781NORTH AMERICAN PHILIPS CORP PROFESSIONAL PRODUCTS DIV
T11-1-15.00A-01-11AL81541SENSATA TECHNOLOGIES MARYLAND, INC


Techincal Specification:
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT POLE ONE
ARC QUENCHING METHODDEION
BODY LENGTH1.375 INCHES NOMINAL
BODY WIDTH0.680 INCHES NOMINAL
BODY STYLESINGLE POLE TYPE
BUSHING LENGTH0.468 INCHES NOMINAL
CASE MATERIALPLASTIC
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH1.125 INCHES NOMINAL
CIRCUIT PROTECTION TYPEOVERCURRENT SINGLE LOCATION
FRAGILITY FACTORMODERATELY RUGGED
FREQUENCY IN HERTZ50.0 OR 60.0 SINGLE LOCATION
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDGENERAL PURPOSE
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP SINGLE LOCATION
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS250.0 AC AND 50.0 DC SINGLE LOCATION
MANUAL ACTUATOR TYPE AND QUANTITY1 TOGGLE
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE15.0 AMPERES AC AND 15.0 AMPERES DC SINGLE LOCATION
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS1000.0 AC AND 1000.0 DC SINGLE LOCATION
MOUNTING FACILITY TYPE AND QUANTITY1 THREADED BUSHING
MOUNTING SURFACE TO TERMINAL END DISTANCE1.702 INCHES NOMINAL
NOMINAL THREAD SIZE0.500 INCHES
NONTURN DEVICE RADIUS0.222 INCHES NOMINAL
NONTURN DEVICE WIDTH0.028 INCHES NOMINAL
POLE QUANTITY1
RESET METHODMANUAL
SPECIAL FEATURESPADDLE HANDLE
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
TERMINAL TYPE AND QUANTITY2 QUICK DISCONNECT, MALE
THREAD QUANTITY PER INCH32
THREAD SERIES DESIGNATORUNS
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT0.100 MINIMUM AT 200 PCT AND 2.000 MAXIMUM AT 200 PCT SINGLE LOCATION
TRIP RELEASE CHARACTERISTICTIME DELAY SINGLE LOCATION
TRIP RELEASE METHODMAGNETIC SINGLE LOCATION
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT138.0 SINGLE LOCATION