CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
45-000-S10-H206402OAKLAND INDUSTRIES LTD
45-000-S10-H2AMP06402OAKLAND INDUSTRIES LTD


Techincal Specification:
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT POLE ONE
ARC QUENCHING METHODMAGNETIC BLOWOUT
BODY STYLESINGLE POLE TYPE
BOSS HEIGHT0.125 INCHES NOMINAL
CASE MATERIALPLASTIC
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH1.125 INCHES NOMINAL
CIRCUIT PROTECTION TYPEOVERCURRENT SINGLE LOCATION
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH1.570 INCHES NOMINAL
FRAGILITY FACTORMODERATELY RUGGED
FREQUENCY IN HERTZ60.0 SINGLE LOCATION
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDGENERAL PURPOSE
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP SINGLE LOCATION
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS240.0 AC AND 24.0 DC SINGLE LOCATION
OVERALL LENGTH1.970 INCHES NOMINAL
OVERALL WIDTH0.730 INCHES NOMINAL
MANUAL ACTUATOR TYPE AND QUANTITY1 PUSH BUTTON
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE2.0 AMPERES AC AND 2.0 AMPERES DC SINGLE LOCATION
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS200.0 AC AND 200.0 DC SINGLE LOCATION
MOUNTING FACILITY TYPE AND QUANTITY2 UNTHREADED HOLE
MOUNTING SURFACE TO TERMINAL END DISTANCE2.170 INCHES NOMINAL
POLE QUANTITY1
RESET METHODMANUAL
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
TERMINAL TYPE AND QUANTITY2 SCREW
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT10.000 MINIMUM AT 200 PCT AND 40.000 MAXIMUM AT 200 PCT SINGLE LOCATION
TRIP RELEASE AMBIENT TEMP RATING70.0 FAHRENHEIT NOMINAL SINGLE LOCATION
TRIP RELEASE CHARACTERISTICTIME DELAY SINGLE LOCATION
TRIP RELEASE METHODTHERMAL SINGLE LOCATION
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT140.0 SINGLE LOCATION
UNPACKAGED UNIT WEIGHT1.000 OUNCES NOMINAL
UNTHREADED MOUNTING HOLE DIAMETER0.180 INCHES NOMINAL