ACTUATOR FUNCTION | TRIP-RESET |
ACTUATOR POSITION DESIGNATION | AT POLE ONE |
ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
BODY LENGTH | 2.500 INCHES NOMINAL |
BODY WIDTH | 0.750 INCHES NOMINAL |
BODY STYLE | SINGLE POLE TYPE |
BOSS HEIGHT | 0.140 INCHES NOMINAL |
CASE MATERIAL | PLASTIC |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.938 INCHES NOMINAL |
CIRCUIT PROTECTION TYPE | OVERCURRENT SINGLE LOCATION |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.062 INCHES NOMINAL |
FEATURES PROVIDED | HIGH INRUSH PROTECTION |
FRAGILITY FACTOR | MODERATELY RUGGED |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | DUSTPROOF AND FUNGUS PROOF |
INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP SINGLE LOCATION |
MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 65.0 DC SINGLE LOCATION |
MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 1000.0 DC SINGLE LOCATION |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 30.0 AMPERES DC SINGLE LOCATION |
MOUNTING FACILITY TYPE AND QUANTITY | 2 THREADED HOLE |
MOUNTING SURFACE TO TERMINAL END DISTANCE | 2.611 INCHES NOMINAL |
NOMINAL THREAD SIZE | 0.138 INCHES |
POLE QUANTITY | 1 |
RESET METHOD | MANUAL |
SPECIAL HANDLING FEATURE | MAGNETIC |
STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
TERMINAL TYPE AND QUANTITY | 2 THREADED STUD |
THREAD QUANTITY PER INCH | 32 |
THREAD SERIES DESIGNATOR | UNC |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 11.000 MINIMUM AT 200 PCT AND 65.000 MAXIMUM AT 200 PCT SINGLE LOCATION |
TRIP RELEASE CHARACTERISTIC | TIME DELAY SINGLE LOCATION |
TRIP RELEASE METHOD | MAGNETIC SINGLE LOCATION |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 SINGLE LOCATION |