ACTUATOR FUNCTION | TRIP-RESET |
ACTUATOR POSITION DESIGNATION | AT POLE TWO |
ADJUSTABLE TRIP SETTING CURRENT RANGE PER POLE IN AMPS | +900.0 TO 1050.0 AC AND +900.0 TO 1050.0 DC ALL LOCATIONS |
AUXILIARY SWITCH FUNCTION AND QUANTITY | 2 ALARM |
BODY HEIGHT | 4.125 INCHES NOMINAL |
BODY LENGTH | 6.500 INCHES NOMINAL |
BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
BODY WIDTH | 4.125 INCHES NOMINAL |
BOSS HEIGHT | 0.188 INCHES NOMINAL |
CASE MATERIAL | PLASTIC |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 5.562 INCHES NOMINAL |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.375 INCHES NOMINAL |
CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 3.312 INCHES NOMINAL |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 1.375 INCHES NOMINAL |
FEATURES PROVIDED | ADJUSTABLE TRIP RELEASE |
FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | GENERAL PURPOSE |
MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 500.0 AC AND 250.0 DC ALL LOCATIONS |
MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 75.0 AMPERES AC AND 75.0 AMPERES DC ALL LOCATIONS |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 15000.0 AC AND 10000.0 DC ALL LOCATIONS |
MOUNTING FACILITY TYPE AND QUANTITY | 4 UNTHREADED HOLE |
POLE QUANTITY | 3 |
RESET METHOD | MANUAL |
TRIP RELEASE AMBIENT TEMP RATING | 50.0 CELSIUS NOMINAL ALL LOCATIONS |
TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS ALL LOCATIONS |
TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 150.0 ALL LOCATIONS |
UNTHREADED MOUNTING HOLE DIAMETER | 0.190 INCHES NOMINAL |
SWITCH LOCATION AND POSITION DESIGNATION | INTERNAL AT POLE ONE AND INTERNAL AT POLE THREE |
SWITCH TERMINAL TYPE | WIRE LEAD |
SWITCH VOLTAGE RATING AND TYPE IN VOLTS | 120.0 AC AND 120.0 DC |
SWITCH CONTACT ARRANGEMENT | SINGLE POLE, DOUBLE THROW |
SWITCH CURRENT RATING AND TYPE IN AMPS | 75.0 AC AND 75.0 DC |
TERMINAL TYPE AND QUANTITY | 6 QUICK DISCONNECT, FEMALE |