ACTUATOR FUNCTION | TRIP-RESET |
ACTUATOR POSITION DESIGNATION | AT POLE TWO |
ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
BODY LENGTH | 12.000 INCHES MAXIMUM |
BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
BODY WIDTH | 8.000 INCHES MAXIMUM |
BOSS HEIGHT | 0.250 INCHES NOMINAL |
CASE MATERIAL | PLASTIC |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 9.875 INCHES NOMINAL |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 3.000 INCHES NOMINAL |
CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 9.750 INCHES NOMINAL |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 3.000 INCHES NOMINAL |
FRAGILITY FACTOR | MODERATELY RUGGED |
FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | GENERAL PURPOSE |
MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 500.0 AC ALL LOCATIONS |
OVERALL HEIGHT | 11.718 INCHES NOMINAL |
MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 175.0 AMPERES AC ALL LOCATIONS |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 100000.0 AC ALL LOCATIONS |
MOUNTING FACILITY TYPE AND QUANTITY | 4 UNTHREADED HOLE |
POLE QUANTITY | 3 |
RESET METHOD | MANUAL |
TRIP RELEASE AMBIENT TEMP RATING | 40.0 CELSIUS NOMINAL ALL LOCATIONS |
TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS ALL LOCATIONS |
TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
UNTHREADED MOUNTING HOLE DIAMETER | 0.438 INCHES NOMINAL |
STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
TERMINAL TYPE AND QUANTITY | 6 THREADED STUD |