5905-01-210-7197 RESISTOR,VARIABLE,WIREWOUND,PRE Index 5999-01-210-7199 SHIELDING GASKET,ELECTRONIC

National Stock Number:
5925-01-210-7198

Federal Supply Class:
5925

National Item Identification Number:
012107198

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
CLA-7082647SENSATA TECHNOLOGIES, INC.


Techincal Specification:
BODY STYLESINGLE POLE TYPE
BODY WIDTH1.875 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH1.062 INCHES NOMINAL
CIRCUIT PROTECTION TYPEOVERCURRENT SINGLE LOCATION
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH2.406 INCHES NOMINAL
FREQUENCY IN HERTZ400.0 SINGLE LOCATION
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDSHOCKPROOF AND VIBRATIONPROOF
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP SINGLE LOCATION
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS110.0 AC AND 30.0 DC SINGLE LOCATION
OVERALL LENGTH3.156 INCHES NOMINAL
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE70.0 AMPERES AC AND 70.0 AMPERES DC SINGLE LOCATION
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS875.0 AC AND 875.0 DC SINGLE LOCATION
MOUNTING FACILITY TYPE AND QUANTITY2 UNTHREADED HOLE
MOUNTING SURFACE TO TERMINAL END DISTANCE1.032 INCHES NOMINAL
POLE QUANTITY1
RESET METHODAUTOMATIC
TRIP RELEASE AMBIENT TEMP RATING77.0 FAHRENHEIT NOMINAL SINGLE LOCATION
TRIP RELEASE CHARACTERISTICTIME DELAY SINGLE LOCATION
TRIP RELEASE METHODTHERMAL SINGLE LOCATION
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT6.000 MINIMUM AT 200 PCT AND 60.000 MAXIMUM AT 200 PCT SINGLE LOCATION
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT130.0 SINGLE LOCATION
UNTHREADED MOUNTING HOLE DIAMETER0.250 INCHES NOMINAL
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
TERMINAL TYPE AND QUANTITY2 SCREW