POLE QUANTITY | 1 |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 0.500 AMPERES AC AND |
| 0.500 AMPERES DC SINGLE LOCATION |
CIRCUIT PROTECTION TYPE | OVERCURRENT SINGLE LOCATION |
TERMINAL TYPE AND QUANTITY | 2 QUICK DISCONNECT, MALE |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 AC AND |
| 50.0 DC SINGLE LOCATION |
TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS SINGLE LOCATION |
RESET METHOD | MANUAL |
BODY STYLE | SINGLE POLE TYPE |
MOUNTING FACILITY TYPE AND QUANTITY | 1 THREADED BUSHING |
CASE MATERIAL | PLASTIC |
UNPACKAGED UNIT WEIGHT | 1.200 OUNCES NOMINAL |
TRIP RELEASE METHOD | MAGNETIC SINGLE LOCATION |
FREQUENCY IN HERTZ | 50.0 OR |
| 60.0 SINGLE LOCATION |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 1000.0 AC AND |
| 1000.0 DC SINGLE LOCATION |
INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP SINGLE LOCATION |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 135.0 SINGLE LOCATION |
MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
BUSHING LENGTH | 0.468 INCHES NOMINAL |
BODY LENGTH | 1.375 INCHES NOMINAL |
BODY WIDTH | 0.680 INCHES NOMINAL |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.125 INCHES NOMINAL |
MOUNTING SURFACE TO TERMINAL END DISTANCE | 1.555 INCHES NOMINAL |
THREAD SERIES DESIGNATOR | UN |
NOMINAL THREAD SIZE | 0.500 INCHES |
THREAD QUANTITY PER INCH | 32 |
MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
ACTUATOR FUNCTION | TRIP-RESET |
ACTUATOR POSITION DESIGNATION | AT POLE ONE |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | GENERAL PURPOSE |
ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
NONTURN DEVICE RADIUS | 0.355 INCHES NOMINAL |
STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
FRAGILITY FACTOR | MODERATELY RUGGED |