POLE QUANTITY | 4 |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 100.0 AMPERES AC FIRST LOCATION |
| 100.0 AMPERES AC SECOND LOCATION |
| 100.0 AMPERES AC THIRD LOCATION |
| 0.0 AMPERES AC FOURTH LOCATION |
CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
TERMINAL TYPE AND QUANTITY | 9 THREADED STUD |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC FIRST LOCATION |
| 240.0 AC SECOND LOCATION |
| 240.0 AC THIRD LOCATION |
| 115.0 AC FOURTH LOCATION |
TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
RESET METHOD | MANUAL |
BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
MOUNTING FACILITY TYPE AND QUANTITY | 8 THREADED HOLE AND |
| 8 SLOT |
CASE MATERIAL | PLASTIC |
TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC ALL LOCATIONS |
FREQUENCY IN HERTZ | 400.0 ALL LOCATIONS |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 5000.0 AC ALL LOCATIONS |
INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP FIRST LOCATION |
| SERIES TRIP SECOND LOCATION |
| SERIES TRIP THIRD LOCATION |
| SHUNT TRIP FOURTH LOCATION |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 40.000 MINIMUM AT 200 PCT AND |
| 105.000 MAXIMUM AT 200 PCT FIRST LOCATION |
| 105.000 MAXIMUM AT 200 PCT SECOND LOCATION |
| 40.000 MINIMUM AT 200 PCT AND |
| 105.000 MAXIMUM AT 200 PCT THIRD LOCATION |
| 0.530 MINIMUM AT 200 PCT AND |
| 1.500 MAXIMUM AT 200 PCT FOURTH LOCATION |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 150.0 ALL LOCATIONS |
MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
BODY LENGTH | 3.544 INCHES NOMINAL |
BODY WIDTH | 4.128 INCHES NOMINAL |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 3.546 INCHES NOMINAL |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.032 INCHES NOMINAL |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.750 INCHES NOMINAL |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 1.032 INCHES NOMINAL |
BOSS HEIGHT | 0.218 INCHES NOMINAL |
MOUNTING SURFACE TO TERMINAL END DISTANCE | 2.609 INCHES NOMINAL |
THREAD SERIES DESIGNATOR | UNC |
NOMINAL THREAD SIZE | 0.138 INCHES |
THREAD QUANTITY PER INCH | 32 |
MOUNTING SLOT WIDTH | 0.164 INCHES NOMINAL |
MANUAL ACTUATOR TYPE AND QUANTITY | 4 TOGGLE |
ACTUATOR FUNCTION | TRIP-RESET |
ACTUATOR POSITION DESIGNATION | AT EACH POLE |
EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE, TWO, THREE, AND FOUR LINKED |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | DUSTPROOF |
ARC QUENCHING METHOD | MAGNETIC BLOWOUT |