Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
203-2-2-51-752-4-1-1A81541SENSATA TECHNOLOGIES MARYLAND, INC


Techincal Specification:
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT POLE ONE
AUXILIARY SWITCH FUNCTION AND QUANTITY1 ALARM
BODY HEIGHT1.770 INCHES MAXIMUM
BODY LENGTH2.000 INCHES NOMINAL
BODY STYLESINGLE POLE TYPE
BODY WIDTH0.920 INCHES NOMINAL
BOSS HEIGHT0.125 INCHES NOMINAL
CASE MATERIALPLASTIC
CIRCUIT PROTECTION TYPEOVERCURRENT SINGLE LOCATION
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP SINGLE LOCATION
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS50.0 DC SINGLE LOCATION
MANUAL ACTUATOR TYPE AND QUANTITY1 TOGGLE
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE7.5 AMPERES DC SINGLE LOCATION
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS1000.0 DC SINGLE LOCATION
MOUNTING FACILITY TYPE AND QUANTITY2 CLIP
POLE QUANTITY1
RESET METHODMANUAL
SPECIAL FEATURESFLUSH MTG HARDWARE INCL; ILLUMINATED HANDLE
TRIP RELEASE CHARACTERISTICTIME DELAY SINGLE LOCATION
TRIP RELEASE METHODMAGNETIC-HYDRAULIC SINGLE LOCATION
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0 SINGLE LOCATION
ULTIMATE TRIP TIME PER POLE IN SECONDS0.200 MINIMUM AND 7.000 MAXIMUM SINGLE LOCATION
SWITCH LOCATION AND POSITION DESIGNATIONEXTERNAL AT POLE ONE
SWITCH TERMINAL TYPETURRET
SWITCH VOLTAGE RATING AND TYPE IN VOLTS50.0 DC
SWITCH CONTACT ARRANGEMENTSINGLE POLE, DOUBLE THROW
SWITCH CURRENT RATING AND TYPE IN AMPS3.0 DC
TERMINAL TYPE AND QUANTITY2 TAB, SOLDER LUG
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT0.050 MINIMUM AT 200 PCT AND 0.950 MAXIMUM AT 200 PCT AND 0.020 MINIMUM AT 400 PCT AND 0.240 MAXIMUM AT 400 PCT SINGLE LOCATION