ACTUATOR FUNCTION | TRIP-RESET |
ACTUATOR POSITION DESIGNATION | AT EACH POLE |
ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
BODY HEIGHT | 2.958 INCHES MINIMUM AND 2.978 INCHES MAXIMUM |
BODY LENGTH | 7.115 INCHES MINIMUM AND 7.135 INCHES MAXIMUM |
BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
BODY WIDTH | 4.490 INCHES MINIMUM AND 4.510 INCHES MAXIMUM |
BOSS HEIGHT | 0.208 INCHES MINIMUM AND 0.228 INCHES MAXIMUM |
CASE MATERIAL | PLASTIC |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 2.797 INCHES MINIMUM AND 2.827 INCHES MAXIMUM |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.500 INCHES NOMINAL |
CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 4.638 INCHES MINIMUM AND 4.668 INCHES MAXIMUM |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 1.490 INCHES MINIMUM AND 1.510 INCHES MAXIMUM |
EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE, TWO, AND THREE LINKED |
FRAGILITY FACTOR | MODERATELY RUGGED |
FREQUENCY IN HERTZ | 47.0 OR 63.0 ALL LOCATIONS |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT AND MOISTURE RESISTANT |
INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP SECOND LOCATION |
INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP W/DUAL RATING FIRST LOCATION |
INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP THIRD LOCATION |
MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 AC AND 90.0 AC FIRST LOCATION |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 AC SECOND LOCATION |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 AC THIRD LOCATION |
MANUAL ACTUATOR TYPE AND QUANTITY | 3 TOGGLE |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 150.0 AMPERES AC ALL LOCATIONS |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 1000.0 AC ALL LOCATIONS |
MOUNTING FACILITY TYPE AND QUANTITY | 4 THREADED HOLE AND 6 UNTHREADED HOLE |
NOMINAL THREAD SIZE | 0.190 INCHES |
POLE QUANTITY | 3 |
RESET METHOD | MANUAL |
SPECIAL HANDLING FEATURE | MAGNETIC |
TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC ALL LOCATIONS |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 15.000 MINIMUM AT 200 PCT AND 95.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
UNTHREADED MOUNTING HOLE DIAMETER | 0.031 INCHES NOMINAL |
STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
TERMINAL TYPE AND QUANTITY | 6 THREADED STUD |
THREAD SERIES DESIGNATOR | UNF |
THREAD QUANTITY PER INCH | 32 |