ACTUATOR FUNCTION | TRIP-RESET |
ACTUATOR POSITION DESIGNATION | AT POLE ONE |
BODY HEIGHT | 1.770 INCHES MAXIMUM |
BODY LENGTH | 2.000 INCHES NOMINAL |
BODY STYLE | SINGLE POLE TYPE |
BODY WIDTH | 0.920 INCHES NOMINAL |
BOSS HEIGHT | 0.125 INCHES NOMINAL |
CASE MATERIAL | PLASTIC |
CIRCUIT PROTECTION TYPE | OVERCURRENT SINGLE LOCATION |
FREQUENCY IN HERTZ | 50.0 OR 60.0 SINGLE LOCATION |
INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP SINGLE LOCATION |
MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 AC SINGLE LOCATION |
MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 1000.0 AC SINGLE LOCATION |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 7.5 AMPERES AC SINGLE LOCATION |
MOUNTING FACILITY TYPE AND QUANTITY | 2 CLIP |
POLE QUANTITY | 1 |
RESET METHOD | MANUAL |
SPECIAL FEATURES | HANDLE EQUIPPED W/NEON BLUB; FLUSH MTG HARDWARE INCL |
TERMINAL TYPE AND QUANTITY | 2 TAB, SOLDER LUG |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 3.000 MINIMUM AT 200 PCT AND 30.000 MAXIMUM AT 200 PCT AND 0.200 MINIMUM AT 400 PCT AND 4.000 MAXIMUM AT 400 PCT AND 0.0350 MINIMUM AT 500 PCT AND 0.900 MAXIMUM AT 500 PCT SINGLE LOCATION |
TRIP RELEASE CHARACTERISTIC | TIME DELAY SINGLE LOCATION |
TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC SINGLE LOCATION |
ULTIMATE TRIP TIME PER POLE IN SECONDS | 20.000 MINIMUM AND 400.000 MAXIMUM SINGLE LOCATION |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 SINGLE LOCATION |