ACTUATOR FUNCTION | RESET |
ACTUATOR POSITION DESIGNATION | AT EACH POLE |
AUXILIARY SWITCH FUNCTION AND QUANTITY | 1 CONTROL |
BODY LENGTH | 5.125 INCHES NOMINAL |
BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
BODY WIDTH | 3.108 INCHES MAXIMUM |
BOSS HEIGHT | 0.220 INCHES NOMINAL |
CASE MATERIAL | PLASTIC |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 3.550 INCHES NOMINAL |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.026 INCHES NOMINAL |
CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.750 INCHES NOMINAL |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 1.026 INCHES NOMINAL |
EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE, TWO, AND THREE LINKED |
FREQUENCY IN HERTZ | 50.0 OR 60.0 ALL LOCATIONS |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT AND MOISTURE RESISTANT |
INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 277.0 AC AND 480.0 AC ALL LOCATIONS |
MANUAL ACTUATOR TYPE AND QUANTITY | 3 TOGGLE |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 0.5 AMPERES AC ALL LOCATIONS |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 5000.0 AC ALL LOCATIONS |
MOUNTING FACILITY TYPE AND QUANTITY | 6 THREADED HOLE |
MOUNTING SURFACE TO TERMINAL END DISTANCE | 3.550 INCHES NOMINAL |
NOMINAL THREAD SIZE | 0.138 INCHES |
SPECIAL FEATURES | ANTI-FLASHOVER BARRIER BETWEEN POLES |
POLE QUANTITY | 3 |
RESET METHOD | MANUAL |
SWITCH CONTACT ARRANGEMENT | SINGLE POLE, DOUBLE THROW |
SWITCH CURRENT RATING AND TYPE IN AMPS | 10.0 AC |
SWITCH LOCATION AND POSITION DESIGNATION | EXTERNAL AT POLE ONE |
SWITCH TERMINAL TYPE | TAB, SOLDER LUG |
SWITCH VOLTAGE RATING AND TYPE IN VOLTS | 250.0 AC |
TERMINAL TYPE AND QUANTITY | 6 THREADED STUD |
THREAD SERIES DESIGNATOR | UNC |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 12.000 MINIMUM AT 125 PCT AND 80.000 MAXIMUM AT 125 PCT AND 2.000 MINIMUM AT 200 PCT AND 10.000 MAXIMUM AT 200 PCT AND 0.400 MINIMUM AT 400 PCT AND 1.800 MAXIMUM AT 400 PCT AND 0.012 MINIMUM AT 1000 PCT AND 0.080 MAXIMUM AT 1000 PCT ALL LOCATIONS |
TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC ALL LOCATIONS |
ULTIMATE TRIP TIME PER POLE IN SECONDS | 80.000 MAXIMUM ALL LOCATIONS |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |