POLE QUANTITY | 3 |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 8.0 AMPERES AC ALL LOCATIONS |
CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
TERMINAL TYPE AND QUANTITY | 6 THREADED STUD |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 120.0 AC ALL LOCATIONS |
TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
RESET METHOD | MANUAL |
BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
MOUNTING FACILITY TYPE AND QUANTITY | 6 CLAMP AND |
| 3 SLOT |
CASE MATERIAL | PLASTIC |
UNPACKAGED UNIT WEIGHT | 2.000 POUNDS NOMINAL |
TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC ALL LOCATIONS |
FREQUENCY IN HERTZ | 50.0 OR |
| 60.0 ALL LOCATIONS |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 5000.0 AC ALL LOCATIONS |
INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 2.000 MINIMUM AT 200 PCT AND |
| 10.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
BODY LENGTH | 5.115 INCHES NOMINAL |
BODY WIDTH | 2.072 INCHES MAXIMUM |
BODY HEIGHT | 4.750 INCHES NOMINAL |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 3.547 INCHES NOMINAL |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.026 INCHES NOMINAL |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.750 INCHES NOMINAL |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 1.026 INCHES NOMINAL |
BOSS HEIGHT | 0.219 INCHES NOMINAL |
THREAD SERIES DESIGNATOR | UNC |
NOMINAL THREAD SIZE | 0.138 INCHES |
THREAD QUANTITY PER INCH | 32 |
MOUNTING SLOT WIDTH | 0.164 INCHES NOMINAL |
MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
ACTUATOR FUNCTION | TRIP-RESET |
ACTUATOR POSITION DESIGNATION | AT EACH POLE |
EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE, TWO, AND THREE LINKED |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT AND |
| MOISTURE RESISTANT |
ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
SPECIAL HANDLING FEATURE | MAGNETIC |
FRAGILITY FACTOR | MODERATELY RUGGED |
SPECIAL FEATURES | T.O. 31P6-2FPS117-24-1; N/H/A POWER DISTRIBUTION PANEL |