ACTUATOR FUNCTION | TRIP-RESET |
ACTUATOR POSITION DESIGNATION | AT POLE ONE |
BODY LENGTH | 2.500 INCHES NOMINAL |
BODY STYLE | SINGLE POLE TYPE |
BODY WIDTH | 0.750 INCHES NOMINAL |
BOSS HEIGHT | 0.140 INCHES NOMINAL |
CASE MATERIAL | PLASTIC |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.938 INCHES NOMINAL |
CIRCUIT PROTECTION TYPE | OVERCURRENT SINGLE LOCATION |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.062 INCHES NOMINAL |
FREQUENCY IN HERTZ | 50.0 SINGLE LOCATION |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT AND MOISTURE RESISTANT |
INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP SINGLE LOCATION |
MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 AC SINGLE LOCATION |
MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 40.0 AMPERES AC SINGLE LOCATION |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 1000.0 AC SINGLE LOCATION |
MOUNTING FACILITY TYPE AND QUANTITY | 2 THREADED HOLE |
MOUNTING SURFACE TO TERMINAL END DISTANCE | 2.611 INCHES NOMINAL |
NOMINAL THREAD SIZE | 0.138 INCHES |
POLE QUANTITY | 1 |
RESET METHOD | MANUAL |
TRIP RELEASE CHARACTERISTIC | TIME DELAY SINGLE LOCATION |
TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC SINGLE LOCATION |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 2.000 MINIMUM AT 200 PCT AND 20.000 MAXIMUM AT 200 PCT AND 0.600 MINIMUM AT 300 PCT AND 5.000 MAXIMUM AT 300 PCT AND 0.300 MINIMUM AT 400 PCT AND 2.000 MAXIMUM AT 400 PCT AND 0.005 MINIMUM AT 1000 PCT AND 0.040 MAXIMUM AT 1000 PCT SINGLE LOCATION |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 SINGLE LOCATION |
ULTIMATE TRIP TIME PER POLE IN SECONDS | 10.000 MINIMUM SINGLE LOCATION |
TERMINAL TYPE AND QUANTITY | 2 THREADED STUD |
THREAD SERIES DESIGNATOR | UNC |
THREAD QUANTITY PER INCH | 32 |