ACTUATOR FUNCTION | TRIP-RESET |
ACTUATOR POSITION DESIGNATION | BETWEEN POLE ONE AND TWO |
BODY LENGTH | 1.500 INCHES MAXIMUM |
BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
BODY WIDTH | 1.250 INCHES MAXIMUM |
BUSHING LENGTH | 0.332 INCHES MINIMUM AND 0.380 INCHES MAXIMUM |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 0.594 INCHES MINIMUM AND 0.656 INCHES MAXIMUM |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.344 INCHES MINIMUM AND 0.406 INCHES MAXIMUM |
CIRCUIT PROTECTION TYPE | OVERCURRENT SECOND LOCATION |
CIRCUIT PROTECTION TYPE | OVERVOLTAGE FIRST LOCATION |
FRAGILITY FACTOR | MODERATELY RUGGED |
FREQUENCY IN HERTZ | 60.0 SECOND LOCATION |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | HERMETICALLY SEALED AND SHOCKPROOF AND VIBRATIONPROOF |
INTERNAL TRIP RELEASE CONFIGURATION | RELAY TRIP SECOND LOCATION |
INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP FIRST LOCATION |
MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
NONTURN DEVICE DIAMETER | 0.250 INCHES NOMINAL |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC SECOND LOCATION |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 50.0 DC FIRST LOCATION |
MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 10.0 AMPERES DC FIRST LOCATION |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 20.0 AMPERES AC SECOND LOCATION |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 1000.0 AC SECOND LOCATION |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 500.0 DC FIRST LOCATION |
MOUNTING FACILITY TYPE AND QUANTITY | 1 THREADED BUSHING W/PANEL SEAL |
MOUNTING SURFACE TO TERMINAL END DISTANCE | 1.780 INCHES MAXIMUM |
NOMINAL THREAD SIZE | 0.375 INCHES |
POLE QUANTITY | 2 |
RESET METHOD | MANUAL |
SPECIAL HANDLING FEATURE | MAGNETIC |
TRIP RELEASE CHARACTERISTIC | TIME DELAY SECOND LOCATION |
TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS FIRST LOCATION |
TRIP RELEASE METHOD | MAGNETIC ALL LOCATIONS |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 120.0 FIRST LOCATION |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 SECOND LOCATION |
UNPACKAGED UNIT WEIGHT | 3.600 OUNCES NOMINAL |
STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
TERMINAL TYPE AND QUANTITY | 5 WIRE HOOK |
THREAD SERIES DESIGNATOR | UNEF |
THREAD QUANTITY PER INCH | 32 |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 0.100 MINIMUM AT 200 PCT AND 0.700 MAXIMUM AT 200 PCT SECOND LOCATION |