ACTUATOR FUNCTION | TRIP-RESET |
ACTUATOR POSITION DESIGNATION | AT POLE ONE |
ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
BODY LENGTH | 1.985 INCHES MINIMUM AND 2.015 INCHES MAXIMUM |
BODY STYLE | SINGLE POLE TYPE |
BODY WIDTH | 0.745 INCHES MINIMUM AND 0.755 INCHES MAXIMUM |
BOSS HEIGHT | 0.125 INCHES MINIMUM AND 0.135 INCHES MAXIMUM |
CASE MATERIAL | PLASTIC |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.555 INCHES MINIMUM AND 1.565 INCHES MAXIMUM |
CIRCUIT PROTECTION TYPE | OVERCURRENT SINGLE LOCATION |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 1.655 INCHES MINIMUM AND 0.665 INCHES MAXIMUM |
FRAGILITY FACTOR | MODERATELY RUGGED |
FREQUENCY IN HERTZ | 60.0 SINGLE LOCATION |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT AND MOISTURE RESISTANT |
INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP SINGLE LOCATION |
MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 AC SINGLE LOCATION |
MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 5.0 AMPERES AC SINGLE LOCATION |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 1000.0 AC SINGLE LOCATION |
MOUNTING FACILITY TYPE AND QUANTITY | 2 TERMINAL |
MOUNTING SURFACE TO TERMINAL END DISTANCE | 1.875 INCHES MINIMUM AND 1.885 INCHES MAXIMUM |
POLE QUANTITY | 1 |
RESET METHOD | MANUAL |
SPECIAL HANDLING FEATURE | MAGNETIC |
TRIP RELEASE CHARACTERISTIC | TIME DELAY SINGLE LOCATION |
TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC SINGLE LOCATION |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 SINGLE LOCATION |
STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
TERMINAL TYPE AND QUANTITY | 2 QUICK DISCONNECT, MALE |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 0.190 MINIMUM AT 200 PCT AND 1.900 MAXIMUM AT 200 PCT SINGLE LOCATION |