ACTUATOR FUNCTION | TRIP-RESET |
ACTUATOR POSITION DESIGNATION | AT EACH POLE |
BODY LENGTH | 2.188 INCHES NOMINAL |
BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
BODY WIDTH | 2.500 INCHES NOMINAL |
BUSHING LENGTH | 0.250 INCHES NOMINAL |
CASE MATERIAL | PLASTIC |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.188 INCHES NOMINAL |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.875 INCHES NOMINAL |
CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 1.812 INCHES NOMINAL |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 0.875 INCHES NOMINAL |
EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE, TWO, AND THREE LINKED |
FREQUENCY IN HERTZ | 400.0 ALL LOCATIONS |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT |
INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 120.0 AC ALL LOCATIONS |
MANUAL ACTUATOR TYPE AND QUANTITY | 3 PUSH-PULL |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 10.0 AMPERES AC ALL LOCATIONS |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 3500.0 AC ALL LOCATIONS |
MOUNTING FACILITY TYPE AND QUANTITY | 6 THREADED HOLE |
MOUNTING SURFACE TO TERMINAL END DISTANCE | 2.000 INCHES MAXIMUM |
NOMINAL THREAD SIZE | 0.138 INCHES |
POLE QUANTITY | 3 |
RESET METHOD | MANUAL |
TRIP RELEASE AMBIENT TEMP RATING | 25.0 CELSIUS NOMINAL ALL LOCATIONS |
TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
TRIP RELEASE METHOD | THERMAL ALL LOCATIONS |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 30.000 MINIMUM AT 200 PCT AND 39.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 138.0 ALL LOCATIONS |
TERMINAL TYPE AND QUANTITY | 6 SCREW |
THREAD SERIES DESIGNATOR | UNC |
THREAD QUANTITY PER INCH | 32 |