4730-01-034-5223 ADAPTER,STRAIGHT,PIPE TO TUBE Index 6610-01-034-5226 INDICATOR,ATTITUDE

National Stock Number:
5925-01-034-5225

Federal Supply Class:
5925

National Item Identification Number:
010345225

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
AP-12-638-381541SENSATA TECHNOLOGIES MARYLAND, INC
AP12-638-398675ESPEY MFG. & ELECTRONICS CORP.
SM-C-66791880063US ARMY COMMUNICATIONS & ELECTRONICS MATERIEL READINESS COMMAND LOGISTICS ENGINEERING DIR


Techincal Specification:
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT POLE ONE
ARC QUENCHING METHODMAGNETIC BLOWOUT
BODY LENGTH1.562 INCHES MAXIMUM
BODY STYLEMULTIPOLE-SINGLE ACTUATOR TYPE
BODY WIDTH1.281 INCHES MAXIMUM
BUSHING LENGTH0.380 INCHES MAXIMUM
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH0.860 INCHES MINIMUM AND 0.890 INCHES MAXIMUM
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH0.610 INCHES MINIMUM AND 0.640 INCHES MAXIMUM
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONS
FRAGILITY FACTORMODERATELY RUGGED
FREQUENCY IN HERTZ47.0 OR 420.0 ALL LOCATIONS
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDHERMETICALLY SEALED AND SHOCK RESISTANT AND VIBRATION RESISTANT
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP SECOND LOCATION
INTERNAL TRIP RELEASE CONFIGURATIONSHUNT TRIP FIRST LOCATION
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS120.0 AC AND 240.0 AC ALL LOCATIONS
MANUAL ACTUATOR TYPE AND QUANTITY1 TOGGLE
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE17.0 AMPERES AC SECOND LOCATION
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS500.0 AC AND 300.0 AC ALL LOCATIONS
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE8.5 AMPERES AC AND 17.0 AMPERES AC FIRST LOCATION
MOUNTING FACILITY TYPE AND QUANTITY1 THREADED BUSHING W/PANEL SEAL
MOUNTING SURFACE TO TERMINAL END DISTANCE1.780 INCHES MAXIMUM
NOMINAL THREAD SIZE0.375 INCHES
NONTURN DEVICE DIAMETER0.235 INCHES MINIMUM AND 0.265 INCHES MAXIMUM
NONTURN DEVICE LENGTH0.130 INCHES NOMINAL
NONTURN DEVICE RADIUS0.610 INCHES MINIMUM AND 0.640 INCHES MAXIMUM
POLE QUANTITY2
RESET METHODMANUAL
SPECIAL HANDLING FEATUREMAGNETIC
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
TERMINAL TYPE AND QUANTITY5 WIRE HOOK
THREAD QUANTITY PER INCH32
THREAD PITCH DIAMETERS+0.3503 TO 0.3537 INCHES
THREAD SERIES DESIGNATORUNEF
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT0.090 MINIMUM AT 200 PCT AND 0.600 MAXIMUM AT 200 PCT SECOND LOCATION
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT0.090 MINIMUM AT 200 PCT AND 1.000 MAXIMUM AT 200 PCT FIRST LOCATION
TRIP RELEASE CHARACTERISTICTIME DELAY ALL LOCATIONS
TRIP RELEASE METHODMAGNETIC ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT115.0 ALL LOCATIONS
UNPACKAGED UNIT WEIGHT3.600 OUNCES NOMINAL


Click here to Register for Free 30-day Trial