ACTUATOR FUNCTION | TRIP-RESET |
ACTUATOR POSITION DESIGNATION | BETWEEN POLE ONE AND TWO |
ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
BODY HEIGHT | 1.770 INCHES MAXIMUM |
BODY LENGTH | 2.000 INCHES NOMINAL |
BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
BODY WIDTH | 1.540 INCHES NOMINAL |
BOSS HEIGHT | 0.250 INCHES NOMINAL |
CASE MATERIAL | PLASTIC |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.625 INCHES NOMINAL |
CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
FRAGILITY FACTOR | MODERATELY RUGGED |
FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT |
INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 120.0 AC ALL LOCATIONS |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 1.0 AMPERES AC ALL LOCATIONS |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 10000.0 AC ALL LOCATIONS |
MOUNTING FACILITY TYPE AND QUANTITY | 2 CLIP |
POLE QUANTITY | 2 |
RESET METHOD | MANUAL |
TERMINAL TYPE AND QUANTITY | 4 QUICK DISCONNECT, MALE |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 0.050 MINIMUM AT 200 PCT AND 1.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC ALL LOCATIONS |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
UNPACKAGED UNIT WEIGHT | 8.500 OUNCES NOMINAL |