DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 4.87501 INCHES NOMINAL |
ACTUATOR FUNCTION | RESET |
BODY HEIGHT | 3.1875 INCHES NOMINAL |
BODY LENGTH | 6.3125 INCHES NOMINAL |
BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
BODY WIDTH | 2.750 INCHES NOMINAL |
BOSS HEIGHT | 0.90625 INCHES NOMINAL |
CASE MATERIAL | PLASTIC |
CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC AND 125.0 DC ALL LOCATIONS |
MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 50.0 AMPERES DC ALL LOCATIONS |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 10000.0 AC AND 5000.0 DC ALL LOCATIONS |
RESET METHOD | MANUAL |
POLE QUANTITY | 2 |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 80.000 MINIMUM AT 200 PCT AND 325.000 MAXIMUM AT 200 PCT AND 30.000 MINIMUM AT 300 PCT AND 130.000 MAXIMUM AT 300 PCT AND 13.000 MINIMUM AT 400 PCT AND 70.000 MAXIMUM AT 400 PCT AND 7.000 MINIMUM AT 500 PCT AND 45.000 MAXIMUM AT 500 PCT AND 13.000 MAXIMUM AT 1000 PCT AND 3.500 MAXIMUM AT 2000 PCT ALL LOCATIONS |
TRIP RELEASE AMBIENT TEMP RATING | 40.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS AND TIME DELAY ALL LOCATIONS |
TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
SPECIAL FEATURES | WITH LINE AND LOAD LUGS |
SUPPLEMENTARY FEATURES | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 250.0 DC IN ADDITION TO CPRF |