ACTUATOR FUNCTION | TRIP-RESET |
ACTUATOR POSITION DESIGNATION | AT POLE ONE |
BODY LENGTH | 1.500 INCHES MAXIMUM |
BODY WIDTH | 0.625 INCHES MAXIMUM |
BODY STYLE | SINGLE POLE TYPE |
BUSHING LENGTH | 0.380 INCHES MAXIMUM |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 0.875 INCHES NOMINAL |
CIRCUIT PROTECTION TYPE | OVERCURRENT SINGLE LOCATION |
FREQUENCY IN HERTZ | 60.0 SINGLE LOCATION |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | HERMETICALLY SEALED |
INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP SINGLE LOCATION |
MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 AC SINGLE LOCATION |
MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 10.0 AMPERES AC SINGLE LOCATION |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 1000.0 AC SINGLE LOCATION |
MOUNTING FACILITY TYPE AND QUANTITY | 1 THREADED BUSHING W/PANEL SEAL |
MOUNTING SURFACE TO TERMINAL END DISTANCE | 1.605 INCHES MAXIMUM |
NOMINAL THREAD SIZE | 0.375 INCHES |
POLE QUANTITY | 1 |
RESET METHOD | MANUAL |
TERMINAL TYPE AND QUANTITY | 2 WIRE HOOK |
THREAD QUANTITY PER INCH | 32 |
THREAD SERIES DESIGNATOR | UNEF |
TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS SINGLE LOCATION |
TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC SINGLE LOCATION |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 150.0 SINGLE LOCATION |