5310-01-022-8120 WASHER,SHOULDERED Index 5925-01-022-8124 CIRCUIT BREAKER

National Stock Number:
5925-01-022-8122

Federal Supply Class:
5925

National Item Identification Number:
010228122

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
TED12404060969GENERAL ELECTRIC CO ELECTRICAL DISTRIBUTION AND CONTROL


Techincal Specification:
CUBIC MEASURE55.314 CUBIC INCHES
FRAGILITY FACTORMODERATELY RUGGED
12.000 MAXIMUM AT 500 PCT AND
0.440 MINIMUM AT 1000 PCT AND
2.400 MAXIMUM AT 1000 PCT AND
0.590 NOMINAL AT 2000 PCT ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0 ALL LOCATIONS
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
BODY LENGTH6.312 INCHES NOMINAL
BODY WIDTH2.750 INCHES NOMINAL
BODY HEIGHT3.140 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH4.620 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH1.380 INCHES NOMINAL
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH4.620 INCHES NOMINAL
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH1.375 INCHES NOMINAL
BOSS HEIGHT0.710 INCHES NOMINAL
MANUAL ACTUATOR TYPE AND QUANTITY1 TOGGLE
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT POLE TWO
ARC QUENCHING METHODAIR
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
POLE QUANTITY2
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE40.0 AMPERES AC AND
40.0 AMPERES DC ALL LOCATIONS
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONS
TERMINAL TYPE AND QUANTITY4 SCREW
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS480.0 AC AND
250.0 DC ALL LOCATIONS
TRIP RELEASE CHARACTERISTICINSTANTANEOUS AND
9.000 MINIMUM AT 300 PCT AND
37.500 MAXIMUM AT 300 PCT AND
4.250 MINIMUM AT 400 PCT AND
18.000 MAXIMUM AT 400 PCT AND
2.400 MINIMUM AT 500 PCT AND
TIME DELAY ALL LOCATIONS
RESET METHODMANUAL
BODY STYLEMULTIPOLE-SINGLE ACTUATOR TYPE
MOUNTING FACILITY TYPE AND QUANTITY4 UNTHREADED HOLE
CASE MATERIALPLASTIC
TRIP RELEASE METHODTHERMAL-MAGNETIC ALL LOCATIONS
FREQUENCY IN HERTZ60.0 ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS18000.0 AC AND
10000.0 DC ALL LOCATIONS
TRIP RELEASE AMBIENT TEMP RATING10.0 DEG CELSIUS MINIMUM AND
50.0 DEG CELSIUS MAXIMUM ALL LOCATIONS
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT725.000 MINIMUM AT 100 PCT AND
1000.000 MAXIMUM AT 100 PCT AND
30.000 MINIMUM AT 200 PCT AND
125.000 MAXIMUM AT 200 PCT AND
15.000 MINIMUM AT 250 PCT AND
60.000 MAXIMUM AT 250 PCT AND