| TIME DELAY ALL LOCATIONS |
RESET METHOD | MANUAL |
BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
CASE MATERIAL | PLASTIC |
TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 18000.0 AC AND |
| 20000.0 DC ALL LOCATIONS |
TRIP RELEASE AMBIENT TEMP RATING | 10.0 DEG CELSIUS MINIMUM AND |
| 50.0 DEG CELSIUS MAXIMUM ALL LOCATIONS |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 88.000 MINIMUM AT 200 PCT AND |
| 350.000 MAXIMUM AT 200 PCT AND |
| 27.500 MINIMUM AT 300 PCT AND |
| 140.000 MAXIMUM AT 300 PCT AND |
| 14.500 MINIMUM AT 400 PCT AND |
| 77.500 MAXIMUM AT 400 PCT AND |
| 7.500 MINIMUM AT 500 PCT AND |
| 47.500 MAXIMUM AT 500 PCT ALL LOCATIONS |
MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
BODY LENGTH | 6.3125 INCHES NOMINAL |
BODY WIDTH | 4.125 INCHES NOMINAL |
BODY HEIGHT | 3.1875 INCHES NOMINAL |
POLE QUANTITY | 3 |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 70.0 AMPERES AC ALL LOCATIONS |
CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
TERMINAL TYPE AND QUANTITY | 3 SCREW BASE |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 600.0 AC AND |
| 250.0 DC ALL LOCATIONS |
TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS AND |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 4.87501 INCHES NOMINAL |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.375 INCHES NOMINAL |
BOSS HEIGHT | 0.90625 INCHES NOMINAL |
MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
ACTUATOR FUNCTION | RESET |
FEATURES PROVIDED | ADJUSTABLE TRIP RELEASE AND |
| INTERCHANGEABLE TRIP RELEASE |