5905-00-994-0315 RESISTOR,VARIABLE,WIRE WOUND,NON Index 5935-00-994-0320 CONNECTOR,RECEPTACLE,ELECTRICAL

National Stock Number:
5925-00-994-0316

Federal Supply Class:
5925

National Item Identification Number:
009940316

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
108-210-10277342TE CONNECTIVITY CORP
108-210-10279405WOOD ELECTRIC OPERATIONS POTTER AND BRUMFIELD DIV AMF INC
2110E79405WOOD ELECTRIC OPERATIONS POTTER AND BRUMFIELD DIV AMF INC
492-210-10277342TE CONNECTIVITY CORP
492-210-10279405WOOD ELECTRIC OPERATIONS POTTER AND BRUMFIELD DIV AMF INC
700-013-1076374SAFRAN ELECTRICAL & POWER USA, LLC
700-013-1081640SAFRAN POWER USA, LLC
BACC18R10B81205THE BOEING COMPANY


Techincal Specification:
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT POLE ONE
BODY LENGTH2.189 INCHES MAXIMUM
BODY STYLESINGLE POLE TYPE
BODY WIDTH0.750 INCHES MAXIMUM
BUSHING LENGTH0.250 INCHES NOMINAL
CASE MATERIALPLASTIC
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH0.704 INCHES NOMINAL
CIRCUIT PROTECTION TYPEOVERCURRENT SINGLE LOCATION
FRAGILITY FACTORMODERATELY RUGGED
FREQUENCY IN HERTZ400.0 SINGLE LOCATION
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDVIBRATION RESISTANT AND SHOCK RESISTANT
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP SINGLE LOCATION
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS120.0 AC AND 30.0 DC SINGLE LOCATION
MANUAL ACTUATOR TYPE AND QUANTITY1 PUSH-PULL
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE10.0 AMPERES AC AND 10.0 AMPERES DC SINGLE LOCATION
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS3500.0 AC AND 6000.0 DC SINGLE LOCATION
MOUNTING FACILITY TYPE AND QUANTITY1 THREADED BUSHING W/PANEL SEAL
MOUNTING SURFACE TO TERMINAL END DISTANCE1.860 INCHES MAXIMUM
NOMINAL THREAD SIZE0.469 INCHES
POLE QUANTITY1
RESET METHODMANUAL
TRIP RELEASE AMBIENT TEMP RATING25.0 CELSIUS NOMINAL SINGLE LOCATION
TRIP RELEASE CHARACTERISTICTIME DELAY SINGLE LOCATION
TRIP RELEASE METHODTHERMAL SINGLE LOCATION
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT15.000 MINIMUM AT 200 PCT AND 55.000 MAXIMUM AT 200 PCT SINGLE LOCATION
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT138.0 SINGLE LOCATION
UNPACKAGED UNIT WEIGHT43.0 GRAMS NOMINAL
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
TERMINAL TYPE AND QUANTITY2 TAB W/SCREW
THREAD SERIES DESIGNATORUNS
THREAD QUANTITY PER INCH32