ACTUATOR FUNCTION | TRIP-RESET |
ACTUATOR POSITION DESIGNATION | AT EACH POLE |
BODY LENGTH | 2.530 INCHES NOMINAL |
BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
BODY WIDTH | 1.530 INCHES NOMINAL |
BOSS HEIGHT | 0.130 INCHES NOMINAL |
CASE MATERIAL | PLASTIC |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.940 INCHES NOMINAL |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.750 INCHES NOMINAL |
CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.060 INCHES NOMINAL |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 0.750 INCHES NOMINAL |
EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE AND TWO LINKED |
INTERNAL TRIP RELEASE CONFIGURATION | RELAY TRIP FIRST LOCATION |
INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP SECOND LOCATION |
MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 28.0 DC ALL LOCATIONS |
MANUAL ACTUATOR TYPE AND QUANTITY | 2 TOGGLE |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 120.0 MILLIAMPERES DC SECOND LOCATION |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 25.0 AMPERES DC FIRST LOCATION |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 3000.0 DC ALL LOCATIONS |
MOUNTING FACILITY TYPE AND QUANTITY | 4 THREADED HOLE |
MOUNTING SURFACE TO TERMINAL END DISTANCE | 2.680 INCHES NOMINAL |
NOMINAL THREAD SIZE | 0.138 INCHES |
POLE QUANTITY | 2 |
RESET METHOD | MANUAL |
TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS AND TIME DELAY ALL LOCATIONS |
TRIP RELEASE METHOD | MAGNETIC ALL LOCATIONS |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
TERMINAL TYPE AND QUANTITY | 6 THREADED STUD |
THREAD SERIES DESIGNATOR | UNC |
THREAD QUANTITY PER INCH | 32 |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 0.180 MINIMUM AT 200 PCT AND 0.500 MAXIMUM AT 200 PCT ALL LOCATIONS |