5905-00-978-7110 RESISTOR,FIXED,FILM Index 5905-00-978-7113 RESISTOR,FIXED,FILM

National Stock Number:
5925-00-978-7112

Federal Supply Class:
5925

National Item Identification Number:
009787112

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
13212E180397403CECOM LR CENTER
ET6270430086L3HARRIS MARITIME POWER & ENERGY SOLUTIONS, INC.
TIP0116597403CECOM LR CENTER


Techincal Specification:
ACTUATOR FUNCTIONTRIP-RESET
AUXILIARY SWITCH FUNCTION AND QUANTITY2 CONTROL
BODY LENGTH10.000 INCHES NOMINAL
BODY STYLEMULTIPOLE-SINGLE ACTUATOR TYPE
BODY WIDTH4.500 INCHES NOMINAL
BOSS HEIGHT0.440 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH8.750 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH1.500 INCHES NOMINAL
CIRCUIT PROTECTION TYPEOVERCURRENT FIRST LOCATION
CIRCUIT PROTECTION TYPEUNDERVOLTAGE SECOND LOCATION
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH8.750 INCHES NOMINAL
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH1.500 INCHES NOMINAL
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITY1 TOGGLE
OVERALL HEIGHT4.840 INCHES NOMINAL
MATERIALPLASTIC CASE
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS10000.0 AC ALL LOCATIONS
MOUNTING FACILITY TYPE AND QUANTITY6 UNTHREADED HOLE
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS600.0 AC ALL LOCATIONS
POLE QUANTITY3
RESET METHODMANUAL
TERMINAL TYPE AND QUANTITY6 SCREW
TRIP RELEASE CHARACTERISTICINSTANTANEOUS ALL LOCATIONS
TRIP RELEASE METHODTHERMAL-MAGNETIC ALL LOCATIONS
UNTHREADED MOUNTING HOLE DIAMETER0.280 INCHES NOMINAL


Click here to Register for Free 30-day Trial