POLE QUANTITY | 1 |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 20.0 AMPERES AC SINGLE LOCATION |
CIRCUIT PROTECTION TYPE | OVERCURRENT SINGLE LOCATION |
TERMINAL TYPE AND QUANTITY | 1 SCREW AND |
| 1 QUICK DISCONNECT, MALE |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 120.0 AC SINGLE LOCATION |
TRIP RELEASE CHARACTERISTIC | TIME DELAY SINGLE LOCATION |
RESET METHOD | MANUAL |
CASE MATERIAL | PLASTIC |
TRIP RELEASE METHOD | THERMAL-MAGNETIC SINGLE LOCATION |
FREQUENCY IN HERTZ | 60.0 SINGLE LOCATION |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 5000.0 AC SINGLE LOCATION |
TRIP RELEASE DUTY CYCLE | CONTINUOUS SINGLE LOCATION |
TRIP RELEASE AMBIENT TEMP RATING | 25.0 DEG CELSIUS NOMINAL SINGLE LOCATION |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 90.000 MINIMUM AT 150 PCT AND |
| 200.000 MAXIMUM AT 150 PCT AND |
| 30.000 MINIMUM AT 200 PCT AND |
| 55.000 MAXIMUM AT 200 PCT AND |
| 14.000 MINIMUM AT 300 PCT AND |
| 26.000 MAXIMUM AT 300 PCT AND |
| 8.000 MINIMUM AT 400 PCT AND |
| 14.000 MAXIMUM AT 400 PCT AND |
| 5.000 MINIMUM AT 500 PCT AND |
| 9.000 MAXIMUM AT 500 PCT SINGLE LOCATION |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 SINGLE LOCATION |
MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
OVERALL LENGTH | 2.843 INCHES NOMINAL |
OVERALL HEIGHT | 2.921 INCHES NOMINAL |
OVERALL WIDTH | 0.968 INCHES NOMINAL |
MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
ACTUATOR FUNCTION | TRIP-RESET |
ACTUATOR POSITION DESIGNATION | AT POLE ONE |
ARC QUENCHING METHOD | DEION |
SPECIAL FEATURES | MOUNTING TYPE IS TERMINAL |
THE MANUFACTURERS DATA | |
MANUFACTURERS CODE | 24446 |
DESIGN CONTROL REFERENCE | TRP1120 |