5961-00-774-2945 SEMICONDUCTOR DEVICE,DIODE Index 5950-00-774-2948 SHUNT WIRING ASSEMBLY

National Stock Number:
5925-00-774-2947

Federal Supply Class:
5925

National Item Identification Number:
007742947

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
154650-00318338XEROX CORP XEROX DOCUMENTATION AND SOFTWARE SERVICES
154650-00356200TYMSHARE INC COMPUTER SUPPORT SERVICES DIV OF MCDONNELL DOUGLAS CORP


Techincal Specification:
ACTUATOR FUNCTIONRESET
ACTUATOR POSITION DESIGNATIONBETWEEN POLE ONE AND TWO
BODY LENGTH2.000 INCHES NOMINAL
BODY STYLEMULTIPOLE-MULTIPLE ACTUATOR TYPE
BODY WIDTH1.500 INCHES NOMINAL
BUSHING LENGTH0.130 INCHES NOMINAL
CASE MATERIALPLASTIC
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH1.530 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH0.750 INCHES NOMINAL
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONS
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH1.660 INCHES NOMINAL
EXTERNAL ACTUATOR LINKAGE ARRANGEMENTONE AND TWO LINKED
FEATURES PROVIDEDHANDLE LOCK
FREQUENCY IN HERTZ60.0 ALL LOCATIONS
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP ALL LOCATIONS
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITY2 TOGGLE
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS240.0 AC ALL LOCATIONS
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE15.0 AMPERES AC ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS1000.0 AC ALL LOCATIONS
MOUNTING FACILITY TYPE AND QUANTITY4 THREADED HOLE
MOUNTING SURFACE TO TERMINAL END DISTANCE2.220 INCHES MAXIMUM
NOMINAL THREAD SIZE0.138 INCHES
POLE QUANTITY2
RESET METHODMANUAL
SWITCH LOCATION AND POSITION DESIGNATIONEXTERNAL AT POLE ONE
SWITCH TERMINAL TYPESOLDER STUD
THREAD SERIES DESIGNATORUNC
THREAD QUANTITY PER INCH32
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT6.000 MINIMUM AT 150 PCT AND 60.000 MAXIMUM AT 150 PCT AND 2.200 MINIMUM AT 200 PCT AND 20.000 MAXIMUM AT 200 PCT AND 0.300 MINIMUM AT 400 PCT AND 2.300 MAXIMUM AT 400 PCT ALL LOCATIONS
TRIP RELEASE CHARACTERISTICTIME DELAY ALL LOCATIONS
TRIP RELEASE METHODMAGNETIC ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0 ALL LOCATIONS
ULTIMATE TRIP TIME PER POLE IN SECONDS175.000 MAXIMUM ALL LOCATIONS