4730-00-761-0100 ADAPTER,STRAIGHT,FLANGE TO TUBE Index 5925-00-761-0105 CIRCUIT BREAKER

National Stock Number:
5925-00-761-0104

Federal Supply Class:
5925

National Item Identification Number:
007610104

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
2226598-210001NAVAIR AND NAVSEA MANAGED ORIGINAL DESIGN ACTIVITY DWG NOT MATERIAL/PARTS SUPPLIER
502A153-R81541SENSATA TECHNOLOGIES MARYLAND, INC
DMS 80042B16236DLA LAND AND MARITIME DBA ENGINEERING AND TECHNICAL SUPPORT DIV DOCUMENT STANDARDIZATION DIVISION (VENDOR ITEM DRAWINGS)


Techincal Specification:
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT POLE ONE
BODY LENGTH1.750 INCHES MAXIMUM
BODY STYLESINGLE POLE TYPE
BODY WIDTH0.625 INCHES MAXIMUM
BUSHING LENGTH0.304 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH0.687 INCHES NOMINAL
CIRCUIT PROTECTION TYPEOVERCURRENT SINGLE LOCATION
FRAGILITY FACTORMODERATELY RUGGED
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDFUNGUS RESISTANT AND HERMETICALLY SEALED
INTERNAL TRIP RELEASE CONFIGURATIONSHUNT TRIP SINGLE LOCATION
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS50.0 DC SINGLE LOCATION
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITY1 TOGGLE
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE15.0 AMPERES DC SINGLE LOCATION
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS500.0 DC SINGLE LOCATION
MOUNTING FACILITY TYPE AND QUANTITY1 THREADED BUSHING
MOUNTING SURFACE TO TERMINAL END DISTANCE1.555 INCHES MAXIMUM
NOMINAL THREAD SIZE0.375 INCHES
POLE QUANTITY1
RESET METHODMANUAL
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
TERMINAL TYPE AND QUANTITY3 WIRE HOOK
THREAD QUANTITY PER INCH32
THREAD SERIES DESIGNATORUNEF
TRIP RELEASE CHARACTERISTICTIME DELAY SINGLE LOCATION
TRIP RELEASE METHODMAGNETIC SINGLE LOCATION
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT10.000 MINIMUM AT 200 PCT AND 40.000 MAXIMUM AT 200 PCT SINGLE LOCATION
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0 SINGLE LOCATION