CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
MATERIAL | PLASTIC CASE |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 30.0 AMPERES AC AND 30.0 AMPERES DC ALL LOCATIONS |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 10000.0 AC ALL LOCATIONS |
MOUNTING FACILITY TYPE AND QUANTITY | 2 UNTHREADED HOLE |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 600.0 AC AND 250.0 DC ALL LOCATIONS |
POLE QUANTITY | 2 |
RESET METHOD | MANUAL |
TERMINAL TYPE AND QUANTITY | 4 SCREW |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 16.000 MINIMUM AT 200 PCT AND 45.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS AND TIME DELAY ALL LOCATIONS |
TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC ALL LOCATIONS |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
ULTIMATE TRIP TIME PER POLE IN SECONDS | 90.000 MINIMUM AND 3600.000 MAXIMUM ALL LOCATIONS |
UNTHREADED MOUNTING HOLE DIAMETER | 0.281 INCHES NOMINAL |