5905-00-682-0740 RESISTOR,VARIABLE,WIRE WOUND,NONPRECISIO Index 5950-00-682-0743 TRANSFORMER,CURRENT

National Stock Number:
5925-00-682-0742

Federal Supply Class:
5925

National Item Identification Number:
006820742

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
13208E5838-297403CECOM LR CENTER
1320BE5838-297403CECOM LR CENTER
72-170-1MG674193EATON CORP HEINEMANN PRODUCTS COMMERCIAL CONTROLS DIV
72-170-1MGL74193EATON CORP HEINEMANN PRODUCTS COMMERCIAL CONTROLS DIV
72-170-2H6674193EATON CORP HEINEMANN PRODUCTS COMMERCIAL CONTROLS DIV
72-170-2MG674193EATON CORP HEINEMANN PRODUCTS COMMERCIAL CONTROLS DIV
APL111-4632-281541SENSATA TECHNOLOGIES MARYLAND, INC
C2191407860BOGUE ELECTRIC MANUFACTURING CO
C219140BXF1BOGUE SYSTEMS INC


Techincal Specification:
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT EACH POLE
BODY LENGTH2.480 INCHES MINIMUM AND 2.500 INCHES MAXIMUM
BODY STYLEMULTIPOLE-MULTIPLE ACTUATOR TYPE
BODY WIDTH2.265 INCHES MAXIMUM
BOSS HEIGHT0.150 INCHES NOMINAL
CASE MATERIALPLASTIC
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH1.940 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH0.750 INCHES NOMINAL
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONS
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH2.050 INCHES MINIMUM AND 2.070 INCHES MAXIMUM
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH0.750 INCHES NOMINAL
EXTERNAL ACTUATOR LINKAGE ARRANGEMENTONE, TWO, AND THREE LINKED
FREQUENCY IN HERTZ400.0 ALL LOCATIONS
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDMOISTURE RESISTANT AND FUNGUS RESISTANT
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP ALL LOCATIONS
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITY3 TOGGLE
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS250.0 AC ALL LOCATIONS
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE41.0 AMPERES AC THIRD LOCATION
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE69.0 AMPERES AC FIRST LOCATION
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE69.0 AMPERES AC SECOND LOCATION
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS1000.0 AC ALL LOCATIONS
MOUNTING FACILITY TYPE AND QUANTITY6 THREADED HOLE
MOUNTING SURFACE TO TERMINAL END DISTANCE2.475 INCHES NOMINAL
NOMINAL THREAD SIZE0.138 INCHES
POLE QUANTITY3
RESET METHODMANUAL
TERMINAL TYPE AND QUANTITY6 THREADED STUD
THREAD SERIES DESIGNATORUNC
THREAD QUANTITY PER INCH32
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT0.200 MINIMUM AT 200 PCT AND 0.600 MAXIMUM AT 200 PCT ALL LOCATIONS
TRIP RELEASE CHARACTERISTICTIME DELAY ALL LOCATIONS
TRIP RELEASE METHODMAGNETIC ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT150.0 ALL LOCATIONS