5905-00-681-3301 RESISTOR,ADJUSTABLE Index 5925-00-681-3307 CIRCUIT BREAKER

National Stock Number:
5925-00-681-3306

Federal Supply Class:
5925

National Item Identification Number:
006813306

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
172083579500WESTINGHOUSE ELECTRIC CORP
172083589946EATON CORPORATION
C218293-206845RAYTHEON COMPANY


Techincal Specification:
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT POLE ONE
ARC QUENCHING METHODDEION
BODY LENGTH2.985 INCHES MINIMUM AND 3.015 INCHES MAXIMUM
BODY STYLESINGLE POLE TYPE
BODY WIDTH1.000 INCHES MAXIMUM
BOSS HEIGHT0.005 INCHES NOMINAL
CASE MATERIALPLASTIC
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH1.796 INCHES MINIMUM AND 1.828 INCHES MAXIMUM
CIRCUIT PROTECTION TYPEOVERCURRENT SINGLE LOCATION
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH2.625 INCHES NOMINAL
FRAGILITY FACTORMODERATELY RUGGED
FREQUENCY IN HERTZ60.0 SINGLE LOCATION
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDGENERAL PURPOSE
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP SINGLE LOCATION
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITY1 TOGGLE
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS125.0 AC AND 32.0 DC SINGLE LOCATION
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE25.0 AMPERES AC AND 25.0 AMPERES DC SINGLE LOCATION
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS5000.0 AC AND 5000.0 DC SINGLE LOCATION
MOUNTING FACILITY TYPE AND QUANTITY2 THREADED HOLE
MOUNTING SURFACE TO TERMINAL END DISTANCE2.554 INCHES MINIMUM AND 2.624 INCHES MAXIMUM
NOMINAL THREAD SIZE0.164 INCHES
POLE QUANTITY1
PRECIOUS MATERIAL AND LOCATIONCONTACT SURFACES SILVER
PRECIOUS MATERIALSILVER
RESET METHODMANUAL
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
TERMINAL TYPE AND QUANTITY2 THREADED STUD
THREAD SERIES DESIGNATORUNC
THREAD QUANTITY PER INCH32
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT12.800 MINIMUM AT 200 PCT AND 38.000 MAXIMUM AT 200 PCT SINGLE LOCATION
TRIP RELEASE AMBIENT TEMP RATING25.0 CELSIUS NOMINAL SINGLE LOCATION
TRIP RELEASE CHARACTERISTICTIME DELAY SINGLE LOCATION
TRIP RELEASE METHODTHERMAL SINGLE LOCATION
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT122.0 SINGLE LOCATION


Click here to Register for Free 30-day Trial