1560-00-535-9636 SLAT ASSY Index 5950-00-535-9645 TRANSFORMER,POWER

National Stock Number:
5925-00-535-9640

Federal Supply Class:
5925

National Item Identification Number:
005359640

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
47503051818PORTA POWER PAK INC
THQL1120GF60967CONTEL BUSINESS NETWORKS INC NETWORK ANALYSIS CENTER
THQL1120GF60969GENERAL ELECTRIC CO ELECTRICAL DISTRIBUTION AND CONTROL
THQL1120GFI60969GENERAL ELECTRIC CO ELECTRICAL DISTRIBUTION AND CONTROL


Techincal Specification:
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT POLE ONE
BODY HEIGHT2.359 INCHES NOMINAL
BODY LENGTH2.844 INCHES NOMINAL
BODY STYLESINGLE POLE TYPE
BODY WIDTH0.969 INCHES NOMINAL
BOSS HEIGHT0.187 INCHES NOMINAL
CIRCUIT PROTECTION TYPEOVERCURRENT SINGLE LOCATION
FRAGILITY FACTORMODERATELY RUGGED
FREQUENCY IN HERTZ60.0 SINGLE LOCATION
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDGENERAL PURPOSE
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITY1 TOGGLE
MATERIALPLASTIC CASE
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE20.0 AMPERES AC SINGLE LOCATION
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS10000.0 AC SINGLE LOCATION
MOUNTING FACILITY TYPE AND QUANTITY2 TERMINAL
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS240.0 AC SINGLE LOCATION
POLE QUANTITY1
RESET METHODMANUAL
SPECIAL FEATURESGROUND FAULT CIRCUIT INTERRUPTER
SPECIAL HANDLING FEATUREMAGNETIC
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
TERMINAL TYPE AND QUANTITY2 BUS BAR
TRIP RELEASE AMBIENT TEMP RATING40.0 CELSIUS NOMINAL SINGLE LOCATION
TRIP RELEASE CHARACTERISTICINSTANTANEOUS SINGLE LOCATION
TRIP RELEASE METHODTHERMAL-MAGNETIC SINGLE LOCATION
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT138.0 SINGLE LOCATION
UNPACKAGED UNIT WEIGHT5.100 OUNCES NOMINAL


Click here to Register for Free 30-day Trial