5925-00-170-4081 CIRCUIT BREAKER Index 5365-00-170-4089 BUSHING

National Stock Number:
5925-00-170-4083

Federal Supply Class:
5925

National Item Identification Number:
001704083

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
GB3-A3-1.75-174193EATON CORP HEINEMANN PRODUCTS COMMERCIAL CONTROLS DIV


Techincal Specification:
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT POLE TWO
ARC QUENCHING METHODMAGNETIC BLOWOUT
BODY LENGTH5.990 INCHES MINIMUM AND 6.010 INCHES MAXIMUM
BODY STYLEMULTIPOLE-SINGLE ACTUATOR TYPE
BODY WIDTH4.490 INCHES MINIMUM AND 4.510 INCHES MAXIMUM
BOSS HEIGHT0.177 INCHES MINIMUM AND 0.197 INCHES MAXIMUM
CASE MATERIALPLASTIC
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH5.115 INCHES MINIMUM AND 5.135 INCHES MAXIMUM
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH1.490 INCHES MINIMUM AND 1.510 INCHES MAXIMUM
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONS
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH4.583 INCHES MINIMUM AND 4.603 INCHES MAXIMUM
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH1.490 INCHES MINIMUM AND 1.510 INCHES MAXIMUM
FRAGILITY FACTORMODERATELY RUGGED
FREQUENCY IN HERTZ60.0 ALL LOCATIONS
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDFUNGUS RESISTANT AND MOISTURE RESISTANT AND SHOCK RESISTANT AND VIBRATION RESISTANT
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP ALL LOCATIONS
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITY1 TOGGLE
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS480.0 AC ALL LOCATIONS
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE1.75 AMPERES AC ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS10000.0 AC ALL LOCATIONS
MOUNTING FACILITY TYPE AND QUANTITY4 UNTHREADED HOLE
MOUNTING SURFACE TO TERMINAL END DISTANCE4.427 INCHES MINIMUM AND 4.447 INCHES MAXIMUM
POLE QUANTITY3
RESET METHODMANUAL
SPECIAL HANDLING FEATUREMAGNETIC
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
TERMINAL TYPE AND QUANTITY6 THREADED STUD
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT30.000 MINIMUM AT 200 PCT AND 250.000 MAXIMUM AT 200 PCT ALL LOCATIONS
TRIP RELEASE CHARACTERISTICTIME DELAY ALL LOCATIONS
TRIP RELEASE METHODMAGNETIC-HYDRAULIC ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0 ALL LOCATIONS
UNPACKAGED UNIT WEIGHT4.000 POUNDS NOMINAL
UNTHREADED MOUNTING HOLE DIAMETER0.256 INCHES MINIMUM AND 0.276 INCHES MAXIMUM