6145-00-167-7505 CABLE,RADIO FREQUENCY Index 5925-00-167-7512 CIRCUIT BREAKER

National Stock Number:
5925-00-167-7511

Federal Supply Class:
5925

National Item Identification Number:
001677511

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
HQNPA307011660WESTINGHOUSE ELECTRIC CORP CONTROL BUSINESS UNIT
HQP3070H11660WESTINGHOUSE ELECTRIC CORP CONTROL BUSINESS UNIT
HQP3070H89946EATON CORPORATION


Techincal Specification:
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT EACH POLE
CASE MATERIALPLASTIC
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONS
FREQUENCY IN HERTZ60.0 ALL LOCATIONS
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDFUNGUS RESISTANT AND MOISTURE RESISTANT
MANUAL ACTUATOR TYPE AND QUANTITY1 TOGGLE
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS240.0 AC ALL LOCATIONS
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE70.0 AMPERES AC ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS10000.0 AC ALL LOCATIONS
POLE QUANTITY3
RESET METHODMANUAL
TRIP RELEASE AMBIENT TEMP RATING40.0 CELSIUS NOMINAL ALL LOCATIONS
TRIP RELEASE CHARACTERISTICINSTANTANEOUS AND TIME DELAY ALL LOCATIONS
TRIP RELEASE METHODTHERMAL-MAGNETIC ALL LOCATIONS


Click here to Register for Free 30-day Trial